Trane RT-PRC010-EN manual Performance 30Ton Data, 1.000

Models: RT-PRC010-EN

1 104
Download 104 pages 11.81 Kb
Page 48
Image 48
Manual background

Performance (30Ton)

Data

Table PD-34 — Supply Fan PerformanceWithVARIABLE FREQUENCY DRIVE orWITHOUT INLETVANES — 30Ton

Cfm

 

 

 

 

 

 

 

Total Static Pressure

 

 

 

 

 

 

 

 

Std

 

.250

 

.500

 

.750

 

1.000

1.250

 

1.500

1.750

2.000

Air

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

6000

316

.50

426

.89

519

1.36

598

1.88

666

2.42

 

728

2.99

784

3.59

835

4.22

7000

334

.65

430

1.05

521

1.56

600

2.12

669

2.71

 

731

3.32

788

3.97

841

4.64

8000

354

.85

440

1.27

523

1.78

602

2.37

671

3.01

 

733

3.67

791

4.36

844

5.08

9000

376

1.09

456

1.54

530

2.06

603

2.66

673

3.33

 

736

4.04

793

4.78

846

5.54

10000

399

1.38

474

1.87

542

2.40

609

3.00

674

3.69

 

737

4.43

795

5.22

849

6.02

11000

424

1.73

493

2.25

558

2.82

619

3.43

679

4.11

 

739

4.86

797

5.68

851

6.53

12000

450

2.13

515

2.70

576

3.30

633

3.93

688

4.62

 

744

5.37

798

6.19

852

7.07

13000

475

2.59

537

3.21

595

3.85

649

4.52

701

5.22

 

753

5.98

804

6.79

854

7.67

13500

488

2.85

549

3.50

605

4.15

658

4.83

709

5.55

 

758

6.32

808

7.13

856

8.01

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cfm

 

 

 

 

 

 

 

Total Static Pressure

 

 

 

 

 

 

 

 

Std

2.250

 

2.500

 

2.750

 

3.000

3.250

 

3.500

3.750

4.000

Air

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

6000

883

4.86

927

5.51

968

6.18

1007

6.86

1043

7.54

 

1078

8.24

1111

8.94

1143

9.65

7000

890

5.33

936

6.04

979

6.78

1020

7.52

1059

8.28

 

1095

9.05

1130

9.83

1164

10.62

8000

894

5.82

941

6.57

985

7.35

1027

8.15

1067

8.97

 

1105

9.80

1142

10.65

1177

11.51

9000

896

6.32

944

7.13

989

7.95

1031

8.79

1072

9.66

 

1111

10.54

1149

11.43

1185

12.35

10000

899

6.85

946

7.70

991

8.57

1034

9.46

1075

10.37

 

1115

11.29

1153

12.24

1189

13.20

11000

901

7.41

949

8.30

994

9.22

1037

10.15

1078

11.11

 

1118

12.08

1156

13.07

1193

14.07

12000

903

7.99

951

8.94

996

9.90

1039

10.88

1080

11.88

 

1120

12.89

1158

13.93

1195

14.98

13000

904

8.61

952

9.60

998

10.61

1041

11.63

1083

12.68

 

1122

13.74

1161

14.82

1198

15.91

13500

905

8.95

953

9.94

998

10.97

1042

12.02

1084

13.09

 

1123

14.18

1162

15.28

1199

16.40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cfm

 

 

 

 

 

 

 

Total Static Pressure

 

 

 

 

 

 

 

 

Std

4.250

 

4.500

 

4.750

 

5.000

5.250

 

5.500

5.750

6.000

Air

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

6000

1174

10.37

1203

11.10

1231

11.83

1259

12.57

1285

13.32

 

1311

14.08

1336

14.85

1361

15.62

7000

1196

11.41

1227

12.22

1256

13.03

1285

13.85

1313

14.68

 

1340

15.51

1366

16.35

 

 

8000

1210

12.38

1243

13.26

1274

14.14

1304

15.04

1333

15.94

 

1361

16.85

 

 

 

 

9000

1219

13.28

1253

14.22

1285

15.18

1316

16.14

1347

17.11

 

1376

18.10

 

 

 

 

10000

1225

14.17

1259

15.16

1292

16.17

1324

17.19

1355

18.23

 

 

 

 

 

 

 

11000

1228

15.09

1263

16.13

1297

17.18

1329

18.25

1361

19.33

 

 

 

 

 

 

 

12000

1231

16.04

1266

17.13

1300

18.22

1333

19.33

1365

20.46

 

 

 

 

 

 

 

13000

1234

17.03

1268

18.15

1302

19.30

1335

20.45

1368

21.62

 

 

 

 

 

 

 

13500

1235

17.53

1270

18.68

1303

19.85

1337

21.03

1369

22.22

 

 

 

 

 

 

 

Notes:

1.Shaded areas at table extremes note non-standard Bhp or Rpm selection. Contact your local Trane representative for more information.

2.Supply fan performance table includes internal resistance of rooftop. For total static pressure determination, system external static must be added to appropriate component static pressure drops (evaporator coil, filters, optional economizer, optional exhaust fan, optional heating system, optional cooling only extended casing, optional roof curb).

3.Minimum motor horsepower is 5 hp, maximum motor horsepower is 20 hp. Maximum RPM is 1379.

4.Max Cfm (for UL approval) as follows: 30 Ton-13,500 Cfm.

5.See RT-EB-104 for further details.

48

RT-PRC010-EN

Page 48
Image 48
Trane RT-PRC010-EN manual Performance 30Ton Data, 1.000