Application Considerations
Horizontal Discharge
The typical rooftop installation has both the supply and return air paths routed through the roof curb and building roof. However, many rooftop installations require horizontal supply and/or return from the rooftop because of a building’s unique design or for acoustic considerations.
Trane has two ways to accomplish horizontal supply and/or return.The first applies to all IntelliPak® Rooftop units. Special field supplied curbs are installed that use the unit’s standard discharge and return openings.The supply and return air is routed through the curb to horizontal openings on the sides of the curb.The second method available for horizontal supply and return applies to
20 - 75 tons SXHF, SFHF, SLHF, SSHF, and
90 - 130 tons SXHG, SLHG and SSHG design units ONLY. With this method the standard discharge and return openings are blocked in the field. Access panels are removed as indicated in Figures
SXHF, SFHF, SLHF, SSHF Units
Figure
used as a unit discharge (see note 1).To return air horizontally, the exhaust fan access door (Panel C) can be removed and used as a return opening.Tables AC- 1, 2 and 3 show dimensions for those panels.
Horizontal Discharge on SXHF, SFHF, SLHF and SSHF Rooftops (20 to 75 tons)
The SXHF (extended casing cooling only), SFHF (gas heat), SSHF (steam heat) and SLHF (hot water heat) rooftops can be field modified to supply and return air horizontally without the use of a horizontal supply/return curb.
To supply air horizontally on SXHF only, the panels that normally house the heat accessory controls (Panel A) and the gas heat barometric dampers (Panel B) can be removed and either of the openings used as a unit discharge.To return air
Figure
Note: Cannot remove Panel A for horizontal discharge on SFHF, SLHF, SSHF Units.
horizontally, the exhaust fan access door (Panel C) can be removed and used as a return opening.
1.For horizontal discharge on SFHF, SLHF and SSHF units, only the Panel B can be removed. Panel A cannot be used due to the location of the heating coils.
2.For horizontal discharge on SFHF (gas heat) models, the block off under the heater must be removed. After removal, a support must be added for the drain tube.
3.Supply and Return Base openings must be covered when converting to a horizontal configuration.
Table |
| Table |
| Table | |||||||||||
| Panel A and B Dimensions |
|
| Panel C Dimensions |
|
|
| X,Y and Z Dimensions |
| ||||||
|
|
| Total Area (H X W) |
|
|
|
| Total Area (H X W) |
|
|
|
|
| ||
Model | H (in.) | W (in.) | (in.2) | (ft2) |
| Model | H (in.) | W (in.) | (in.2) | (ft2) |
| Model | X (in.) | Y (in.) | Z (in.) |
S*HF C20 | 40.7 | 25.5 | 1038 | 7.2 |
| S*HF C20 | 40.7 | 34.5 | 1404 | 9.8 |
| S*HF C20 | 35.5 | 44.0 | 201.5 |
S*HF C25 | 40.7 | 25.5 | 1038 | 7.2 |
| S*HF C25 | 40.7 | 34.5 | 1404 | 9.8 |
| S*HF C25 | 35.5 | 44.0 | 201.5 |
S*HF C30 | 52.7 | 25.5 | 1344 | 9.3 |
| S*HF C30 | 52.7 | 34.5 | 1818 | 12.6 |
| S*HF C30 | 35.5 | 56.0 | 201.5 |
S*HF C40 | 64.5 | 34.5 | 2225 | 15.5 |
| S*HF C40 | 64.5 | 34.5 | 2225 | 15.5 |
| S*HF C40 | 44.5 | 67.8 | 237.0 |
S*HF C50 | 76.7 | 34.5 | 2646 | 18.4 |
| S*HF C50 | 76.7 | 34.5 | 2646 | 18.4 |
| S*HF C50 | 44.5 | 80.0 | 237.0 |
S*HF C55 | 76.7 | 34.5 | 2646 | 18.4 |
| S*HF C55 | 76.7 | 34.5 | 2646 | 18.4 |
| S*HF C55 | 44.5 | 80.0 | 237.0 |
S*HF C60 | 64.6 | 34.5 | 2229 | 15.5 |
| S*HF C60 | 64.6 | 34.5 | 2229 | 15.5 |
| S*HF C60 | 44.5 | 68.0 | 237.5 |
S*HF C70 | 64.6 | 34.5 | 2229 | 15.5 |
| S*HF C70 | 64.6 | 34.5 | 2229 | 15.5 |
| S*HF C70 | 44.5 | 68.0 | 237.5 |
S*HF C75 | 64.6 | 34.5 | 2229 | 15.5 |
| S*HF C75 | 64.6 | 34.5 | 2229 | 15.5 |
| S*HF C75 | 44.5 | 68.0 | 237.5 |
Notes: |
|
|
|
|
| * = X, F , L, or S |
|
|
|
|
|
|
|
|
1.Add an extra
2.The openings all have a
3.If exhaust fans are being used, provisions should be made for access to the exhaust components, since the access door is now being used as a return.
4.Use the dimensions provided and the supply Cfm to calculate the velocity (ft/min) through the openings to be sure they are acceptable.
11 |