Table GD-1— General Data — 20-40Tons Continued

General Data

Table GD-1— General Data — 20-40Tons Continued

 

20Ton

25Ton

30Ton

40Ton

Filters

 

 

 

 

Panel Filters

 

 

 

 

Number/Size (Inches)

12 — 20x20x2

12 — 20x20x2

16 — 20x20x2

16 — 20x25x2

Face Area (Ft2)

33.3

33.3

44.4

55.5

Bag Filters

 

 

 

 

Number/Size (Inches)

4 — 12x24x19

4 — 12x24x19

2 — 12x24x19

5 — 12x24x19

 

3 — 24x24x19

3 — 24x24x19

6 — 24x24x19

6 — 24x24x19

Cartridge Filters

4 — 12x24x12

4 — 12x24x12

2 — 12x24x12

5 — 12x24x12

 

3 — 24x24x12

3 — 24x24x12

6 — 24x24x12

6 — 24x24x12

Prefilters (For Bag & Cartridge)

4 — 12x24x2

4 — 12x24x2

2 — 12x24x2

5 — 12x24x2

 

3 — 24x24x2

3 — 24x24x2

6 — 24x24x2

6 — 24x24x2

Face Area (Ft2)

20.0

20.0

28.0

34.0

Standard Unit Minimum Outside AirTemperature For Mechanical Cooling

 

 

Without Hot Gas Option

55 F

50 F

50 F

55 F

With Hot Gas Option

55 F

50 F

50 F

55 F

Low Ambient Option Minimum Outside AirTemperature

 

 

 

Without Hot Gas Option

0 F

0 F

0 F

0 F

With Hot Gas Option

10 F

10 F

10 F

10 F

Notes:

1.For cfm values outside these ranges, refer to RT-EB-104.

2.Refer to Table PD-30 for availability of electric heat kw ranges by voltage.

3.20-30 Ton models are single circuit, 40 Ton models are dual circuit.

4.The firing rate of the unit can vary from 33% of the Heater Mbh up to the nameplate rating of the unit.

5.The firing rate of the unit can vary from pilot rate of 125,000 Btuh up to the nameplate rating of the unit.

RT-PRC010-EN

23

Page 23
Image 23