Trane RT-PRC010-EN manual Application Considerations, Duct Design, Improper, Proper

Models: RT-PRC010-EN

1 104
Download 104 pages 11.81 Kb
Page 15
Image 15
Duct Design

Application Considerations

Duct Design

It is important to note that the rated capacities of the rooftop can be met only if the rooftop is properly installed in the field. A well-designed duct system is essential in meeting these capacities.

The satisfactory distribution of air throughout the system requires that there be an unrestricted and uniform airflow from the rooftop discharge duct. This discharge section should be straight for at least several duct diameters to allow the conversion of fan energy from velocity pressure to static pressure.

However, when job conditions dictate elbows be installed near the rooftop outlet, the loss of capacity and static pressure may be reduced through the use of guide vanes and proper direction of the bend in the elbow.The high velocity side of the rooftop outlet should be directed at the outside radius of the elbow rather than the inside as illustrated in Figure AC-5.

Figure AC-4 — Unit Placement

1

ImproperProperManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background 2

1. 20-40 ton models have only one outdoor air intake. 50 - 75 ton models have two outdoor air intakes.

2. 90-130 ton models have two outdoor air intakes on the backside of the unit and one small air intake at the end of the unit.

Figure AC-5 — Duct Design

Improper

Proper

RT-PRC010-EN

15

Page 15
Image 15
Trane RT-PRC010-EN manual Application Considerations, Duct Design, Improper, Proper