Trane RT-PRC010-EN Controls, VAV Units Only, Sequence Of Operation, Inlet GuideVanes Control

Models: RT-PRC010-EN

1 104
Download 104 pages 11.81 Kb
Page 75
Image 75
Controls

Controls

(VAV Units)

 

 

 

 

VAV Units Only

Sequence Of Operation

NOTE: When noted in this sequence “Human Interface Panel,” the reference is to both the unit mounted and remote mounted Human Interface Panel. All setpoint adjustments can be accomplished at the unit or Remote Human Interface Panel.

1

Supply Air Pressure Control

Inlet GuideVanes Control

Inlet guide vanes are driven by a modulating 0-10 vdc signal from the Rooftop Module (RTM). A pressure transducer measures duct static pressure, and the inlet guide vanes are modulated to maintain the supply air static pressure within an adjustable user- defined range.The range is determined by the supply air pressure setpoint and supply air pressure deadband, which are set through the Human Interface Panel.

Inlet guide vane assemblies installed on the supply fan inlets regulate fan capacity and limit horsepower at lower system air requirements. When in any position other than full open, the vanes pre-spin intake air in the same direction as supply fan rotation. As the vanes approach the full-closed position, the amount of “spin” induced by the vanes increases at the same time that intake airflow and fan horsepower diminish. The inlet guide vanes will close when the supply fan is shut down, except during night setback.

Variable Frequency Drive (VFD) Control

Variable frequency drives are driven by a modulating 0-10 vdc signal from the Rooftop Module (RTM). A pressure transducer measures duct static pressure, and the VFD is modulated to maintain the supply air static pressure within an adjustable user-defined range. The range is determined by the supply air pressure setpoint and supply air pressure deadband, which are set through the Human Interface Panel.

Variable frequency drives provide supply fan motor speed modulation.The drive will accelerate or decelerate as required to maintain the supply static pressure setpoint. When subjected to high ambient return conditions the VFD shall reduce its output frequency to maintain operation. Bypass control is offered to provide full nominal airflow in the event of drive failure.

Supply Air Static Pressure Limit

The opening of the inlet guide vanes and VAV boxes are coordinated during unit start up and transition to/from Occupied/ Unoccupied modes to prevent overpressurization of the supply air ductwork. However, if for any reason the supply air pressure exceeds the user- defined supply air static pressure limit that was set at the Human Interface Panel, the supply fan/VFD is shut down and the inlet guide vanes (if included) are closed.The unit is then allowed to restart three times. If the overpressurization condition occurs on the third time, the unit is shut down and a manual reset diagnostic is set and displayed at the Human Interface Panel.

2

Supply AirTemperature Controls

Cooling/Economizer

During Occupied cooling mode of operation, the economizer (if available) and mechanical cooling are used to control the supply air temperature.The supply air temperature setpoint and deadband are user-defined at the Human Interface Panel. If the enthalpy of the outside air is appropriate to use “free cooling,” the economizer will be used first to attempt to satisfy the supply air setpoint; then if required the mechanical cooling will be staged on to maintain supply air temperature setpoint. Minimum On/Off timing of

the mechanical cooling prevents rapid cycling.

On units with economizer, a call for cooling will modulate the fresh air dampers open.The rate of economizer modulation is based on deviation of the discharge temperature from setpoint, i.e., the further away from setpoint, the faster the fresh air damper will open. First stage of cooling will be allowed to start after the economizer reaches

full open.

Note that the economizer is only allowed to function freely if one of the following conditions is met. For dry bulb economizer control the ambient temperature must be below the dry bulb temperature control setting. For reference enthalpy economizer control, outdoor air enthalpy must be below the enthalpy control setting. For comparative enthalpy economizer control, outdoor air enthalpy must be below the enthalpy of the return air.

At outdoor air conditions above the enthalpy control setting, mechanical cooling only is used and the fresh air dampers remain at minimum position.

If the unit does not include an economizer, mechanical cooling only is used to satisfy cooling requirements. Outdoor air dampers may be set manually for a maximum of 25 percent outdoor air, if rooftop is equipped with 0 to 25 percent manual fresh air damper.

RT-PRC010-EN

75

Page 75
Image 75
Trane RT-PRC010-EN Controls, VAV Units Only, Sequence Of Operation, Supply Air Pressure Control, Cooling/Economizer