*UH2C100A9V4V FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

 

 

 

 

 

 

 

 

 

 

 

 

1st Stage Capacity =

62,855

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2nd Stage Capacity =

96,700

 

 

 

 

 

 

 

 

 

AIRFLOW

DIP SWITCH SETTING

 

 

 

 

 

EXTERNAL STATIC PRESSURE

 

 

 

 

SETTING

 

SW 7

 

SW8

 

 

 

 

0.1

0.3

0.5

 

0.7

 

 

0.9

 

 

 

 

 

 

 

 

 

 

CFM

 

873

893

900

 

899

 

 

902

 

 

 

LOW

 

ON

 

ON

TEMP. RISE

 

64

63

62

 

62

 

 

62

 

 

 

 

 

 

 

 

 

WATTS

 

100

145

195

 

240

 

 

290

 

 

 

 

 

 

 

 

 

 

CFM

 

971

997

1006

 

1022

 

 

1029

 

 

HEATING

MEDIUM LOW

 

OFF

 

ON

TEMP. RISE

 

58

56

56

 

55

 

 

54

 

 

 

 

 

 

 

 

WATTS

 

115

170

220

 

280

 

 

335

 

 

1ST

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

1136

1146

1165

 

1180

 

 

1184

 

 

STAGE

 

 

 

 

 

 

 

 

 

 

 

 

 

MEDIUM **

 

ON

 

OFF

TEMP. RISE

 

49

49

48

 

47

 

 

47

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WATTS

 

160

230

295

 

365

 

 

425

 

 

 

 

 

 

 

 

 

 

CFM

 

1258

1298

1319

 

1328

 

 

1286

 

 

 

HIGH

 

OFF

 

OFF

TEMP. RISE

 

44

43

42

 

42

 

 

44

 

 

 

 

 

 

 

 

 

WATTS

 

225

300

390

 

450

 

 

490

 

 

 

 

 

 

 

 

 

 

CFM

 

1260

1304

1329

 

1334

 

 

1317

 

 

 

LOW

 

ON

 

ON

TEMP. RISE

 

68

66

65

 

65

 

 

65

 

 

 

 

 

 

 

 

 

WATTS

 

213

305

380

 

460

 

 

510

 

 

 

 

 

 

 

 

 

 

CFM

 

1464

1471

1478

 

1478

 

 

1350

 

 

HEATING

MEDIUM LOW

 

OFF

 

ON

TEMP. RISE

 

59

59

58

 

58

 

 

64

 

 

 

 

 

 

 

 

WATTS

 

315

405

485

 

560

 

 

540

 

 

2ND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

1631

1678

1690

 

1579

 

 

1419

 

 

STAGE

 

 

 

 

 

 

 

 

 

 

 

 

 

MEDIUM **

 

ON

 

OFF

TEMP. RISE

 

53

51

51

 

55

 

 

61

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WATTS

 

450

570

670

 

645

 

 

585

 

 

 

 

 

 

 

 

 

 

CFM

 

1846

1867

1794

 

1644

 

 

1498

 

 

 

HIGH

 

OFF

 

OFF

TEMP. RISE

 

47

46

48

 

52

 

 

57

 

 

 

 

 

 

 

 

 

WATTS

 

640

760

770

 

700

 

 

650

 

 

NOTES: * First letter may be "A" or "T"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

** Factory setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*UH2C100A9V4V FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

 

OUTDOOR

AIRFLOW

 

 

DIP SWITCH SETTING

 

 

EXTERNAL STATIC PRESSURE

 

UNIT SIZE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SETTING

 

 

 

 

 

 

 

 

 

 

 

0.1

0.3

0.5

 

0.7

0.9

 

 

(TONS)

 

SW 1

 

SW 2

 

SW 3

 

SW 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW

 

ON

 

ON

 

OFF

 

ON

CFM

 

808

824

840

 

835

830

 

 

 

(350 CFM/TON)

 

 

 

 

WATTS

 

75

125

170

 

210

250

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5

NORMAL

 

ON

 

ON

 

OFF

 

OFF

CFM

 

938

963

959

 

964

975

 

 

(400 CFM/TON)

 

 

 

 

WATTS

 

100

160

205

 

255

310

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH

 

ON

 

ON

 

ON

 

OFF

CFM

 

1058

1100

1121

 

1136

1142

 

 

 

(450 CFM/TON)

 

 

 

 

WATTS

 

150

200

265

 

330

395

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW

 

OFF

 

ON

 

OFF

 

ON

CFM

 

1004

1010

1027

 

1044

1050

 

 

 

(350 CFM/TON)

 

 

 

 

WATTS

 

120

175

230

 

285

345

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.0

NORMAL

 

OFF

 

ON

 

OFF

 

OFF

CFM

 

1141

1190

1214

 

1229

1234

 

 

(400 CFM/TON)

 

 

 

 

WATTS

 

170

245

310

 

380

450

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH

 

OFF

 

ON

 

ON

 

OFF

CFM

 

1336

1375

1387

 

1388

1384

 

 

 

(450 CFM/TON)

 

 

 

 

WATTS

 

250

330

410

 

480

545

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW

 

ON

 

OFF

 

OFF

 

ON

CFM

 

1153

1206

1230

 

1239

1244

 

 

 

(350 CFM/TON)

 

 

 

 

WATTS

 

180

250

320

 

395

460

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.5

NORMAL

 

ON

 

OFF

 

OFF

 

OFF

CFM

 

1390

1418

1439

 

1441

1373

 

 

(400 CFM/TON)

 

 

 

 

WATTS

 

285

465

445

 

515

540

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH

 

ON

 

OFF

 

ON

 

OFF

CFM

 

1575

1606

1632

 

1596

1445

 

 

 

(450 CFM/TON)

 

 

 

 

WATTS

 

400

495

590

 

645

590

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW

 

OFF

 

OFF

 

OFF

 

ON

CFM

 

1388

1423

1444

 

1444

1390

 

 

 

(350 CFM/TON)

 

 

 

 

WATTS

 

290

360

440

 

515

540

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.0

NORMAL

 

OFF

 

OFF

 

OFF

 

OFF

CFM

 

1610

1641

1666

 

1607

1449

 

 

(400 CFM/TON)

 

 

 

 

WATTS

 

415

515

635

 

650

595

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH

 

OFF

 

OFF

 

ON

 

OFF

CFM

 

1847

1863

1816

 

1687

1532

 

 

 

(450 CFM/TON)

 

 

 

 

WATTS

 

630

735

780

 

720

665

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES: *First letter may be "A" or "T"

1.At Continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value.

2.LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting; NORMAL airflow (400 cfm/ton) is typical setting;

HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.

12

Pub. No. 22-1814-08

Page 12
Image 12
Trane TUH2B080A9V3VA, TUH2C100A9V5VA, TUH2C100A9V4VA manual Airflow DIP Switch Setting External Static Pressure SW8 CFM

TDH2B060A9V3VA, TDH2B080A9V4VA, TDH2B080A9V3VA, TDH2D120A9V5VA, TDH2C100A9V4VA specifications

Trane is renowned for its commitment to energy efficiency, innovation, and reliability, exemplified in its range of TUH2 series air handlers. Among these models, the TUH2C100A9V5VA, TUH2C100A9V4VA, TUH2D120A9V5VA, TUH2B080A9V3VA, and TUH2B080A9V4VA stand out with their advanced features and technologies designed to enhance indoor comfort and operational efficiency.

The TUH2C100A9V5VA and TUH2C100A9V4VA are both equipped for versatile applications, making them suitable for residential and light commercial purposes. These models feature a durable construction that ensures longevity even in demanding environments. Their design incorporates a high-efficiency blower that allows for optimized airflow, ensuring a balanced temperature throughout the space.

The TUH2D120A9V5VA model is tailored specifically for larger applications, providing enhanced performance and increased capacity. Its dual-stage heating function guarantees consistent warmth during colder months, while the integrated energy recovery ventilator contributes to improved indoor air quality by allowing for better ventilation. This model is particularly beneficial in increasingly energy-conscious markets, demonstrating Trane's commitment to sustainability.

Both the TUH2B080A9V3VA and TUH2B080A9V4VA are designed for maximum efficiency in smaller applications. They utilize variable speed technology, allowing them to adjust the airflow according to fluctuating demand. This efficient operation not only reduces energy consumption but also minimizes noise levels, creating a more comfortable and peaceful indoor environment.

All models in the TUH2 series feature advanced diagnostics and communication capabilities, enabling remote monitoring and management of the systems. This technology helps property owners track performance and energy usage in real-time, facilitating proactive maintenance and improving overall system reliability.

Trane's TUH2 series is built with a focus on quality and innovation, utilizing high-grade materials to withstand various environmental factors. Each unit is engineered for easy installation and maintenance, ensuring that technicians can efficiently service these robust systems. In summary, the TUH2 series air handlers provide a blend of performance, efficiency, and user-friendly features, making them an excellent choice for any indoor climate control needs.