*UH2B080A9V3V FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

 

 

 

 

 

 

 

 

 

1st Stage Capacity =

50,440

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2nd Stage Capacity =

77,600

 

 

 

 

 

 

 

AIRFLOW

DIP SWITCH SETTING

 

 

 

 

 

EXTERNAL STATIC PRESSURE

 

 

SETTING

 

SW 7

SW 8

 

 

 

 

0.1

0.3

 

0.5

 

 

0.7

 

0.9

 

 

 

 

 

 

 

CFM

800

800

 

800

 

 

800

 

800

 

LOW

 

ON

ON

 

TEMP. RISE

56

56

 

56

 

 

56

 

56

 

 

 

 

 

 

 

WATTS

105

140

 

180

 

 

220

 

265

 

 

 

 

 

 

 

CFM

860

880

 

890

 

 

920

 

910

 

MEDIUM LOW

 

OFF

ON

 

TEMP. RISE

52

51

 

50

 

 

48

 

49

HEATING

 

 

 

 

 

 

WATTS

115

165

 

215

 

 

265

 

320

1ST

 

 

 

 

 

 

CFM

960

990

 

1000

 

 

1020

 

1010

STAGE

 

 

 

 

 

TEMP. RISE

 

 

 

 

NORMAL **

 

ON

OFF

 

46

45

 

44

 

 

44

 

44

 

 

 

 

WATTS

 

 

 

 

 

 

 

 

 

 

 

150

200

 

230

 

 

310

 

350

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

1080

1110

 

1120

 

 

1120

 

1080

 

HIGH

 

OFF

OFF

 

TEMP. RISE

41

40

 

40

 

 

40

 

41

 

 

 

 

 

 

 

WATTS

195

255

 

315

 

 

365

 

390

 

LOW

 

ON

ON

 

 

CFM

1100

1100

 

1120

 

 

1120

 

1090

 

 

 

TEMP. RISE

62

62

 

61

 

 

61

 

63

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WATTS

205

260

 

320

 

 

370

 

400

 

MEDIUM LOW

 

OFF

ON

 

 

CFM

1210

1240

 

1260

 

 

1260

 

1130

 

 

 

TEMP. RISE

57

55

 

54

 

 

54

 

61

HEATING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WATTS

265

340

 

410

 

 

470

 

430

2ND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

1360

1390

 

1400

 

 

1360

 

1210

STAGE

NORMAL **

 

ON

OFF

 

 

 

 

 

 

 

 

TEMP. RISE

50

49

 

49

 

 

50

 

57

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WATTS

365

445

 

500

 

 

535

 

475

 

 

 

 

 

 

 

CFM

1360

1390

 

1400

 

 

1350

 

1180

 

HIGH

 

OFF

OFF

 

TEMP. RISE

50

49

 

49

 

 

51

 

58

 

 

 

 

 

 

 

WATTS

355

450

 

520

 

 

535

 

465

NOTES: * First letter may be "A" or "T"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

** Factory setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*UH2B080A9V3V FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR

AIRFLOW

 

DIP SWITCH SETTING

 

 

EXTERNAL STATIC PRESSURE

UNIT SIZE

SETTING

 

SW 1

SW 2

SW 3

 

SW 4

 

 

0.1

 

0.3

0.5

 

0.7

 

0.9

(TONS)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW

 

ON

ON

OFF

 

ON

CFM

 

750

 

750

750

 

720

 

710

 

(350 CFM/TON)

 

 

WATTS

 

84

 

122

154

 

185

 

221

 

 

 

 

 

 

 

 

 

 

 

 

2.0

NORMAL

 

ON

ON

OFF

 

OFF

CFM

 

840

 

840

840

 

840

 

820

(400 CFM/TON)

 

 

WATTS

 

109

 

146

181

 

226

 

264

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH

 

ON

ON

ON

 

OFF

CFM

 

940

 

940

940

 

940

 

940

 

(450 CFM/TON)

 

 

WATTS

 

136

 

177

215

 

274

 

318

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW

 

OFF

ON

OFF

 

ON

CFM

 

850

 

850

870

 

890

 

890

 

(350 CFM/TON)

 

 

WATTS

 

113

 

150

200

 

250

 

295

 

 

 

 

 

 

 

 

 

 

 

 

2.5

NORMAL

 

OFF

ON

OFF

 

OFF

CFM

 

960

 

990

1000

 

1020

1010

(400 CFM/TON)

 

 

WATTS

 

150

 

200

230

 

305

 

350

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH

 

OFF

ON

ON

 

OFF

CFM

 

1080

 

1110

1120

 

1120

1080

 

(450 CFM/TON)

 

 

WATTS

 

195

 

255

315

 

365

 

390

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW

 

ON

OFF

OFF

 

ON

CFM

 

1020

 

1020

1040

 

1050

1050

 

(350 CFM/TON)

 

 

WATTS

 

175

 

225

280

 

330

 

375

 

 

 

 

 

 

 

 

 

 

 

 

3.0

NORMAL

 

ON

OFF

OFF

 

OFF

CFM

 

1170

 

1180

1200

 

1200

1130

(400 CFM/TON)

 

 

WATTS

 

240

 

300

365

 

415

 

420

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH

 

ON

OFF

ON

 

OFF

CFM

 

1290

 

1320

1350

 

1340

1150

 

(450 CFM/TON)

 

 

WATTS

 

310

 

410

470

 

520

 

440

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW

 

OFF

OFF

OFF

 

ON

CFM

 

1170

 

1190

1210

 

1210

1100

 

(350 CFM/TON)

 

 

WATTS

 

250

 

315

370

 

435

 

405

 

 

 

 

 

 

 

 

 

 

 

 

3.5

NORMAL

 

OFF

OFF

OFF

 

OFF

CFM

 

1360

 

1390

1400

 

1360

1210

(400 CFM/TON)

 

 

WATTS

 

365

 

445

500

 

535

 

475

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH

 

OFF

OFF

ON

 

OFF

CFM

 

1360

 

1390

1400

 

1350

1180

 

(450 CFM/TON)

 

 

WATTS

 

355

 

450

520

 

535

 

460

 

 

 

 

 

 

 

 

 

 

 

 

NOTES: * First letter may be "A" or "T"

1.At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value.

2.LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting; NORMAL airflow (400 cfm/ton) is typical setting;

HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.

10

Pub. No. 22-1814-08

Page 10
Image 10
Trane TUH2C100A9V5VA, TUH2C100A9V4VA, TUH2B080A9V3VA, TUH2D120A9V5VA, TUH2B080A9V4VA manual Medium LOW OFF TEMP. Rise Heating

TDH2B060A9V3VA, TDH2B080A9V4VA, TDH2B080A9V3VA, TDH2D120A9V5VA, TDH2C100A9V4VA specifications

Trane is renowned for its commitment to energy efficiency, innovation, and reliability, exemplified in its range of TUH2 series air handlers. Among these models, the TUH2C100A9V5VA, TUH2C100A9V4VA, TUH2D120A9V5VA, TUH2B080A9V3VA, and TUH2B080A9V4VA stand out with their advanced features and technologies designed to enhance indoor comfort and operational efficiency.

The TUH2C100A9V5VA and TUH2C100A9V4VA are both equipped for versatile applications, making them suitable for residential and light commercial purposes. These models feature a durable construction that ensures longevity even in demanding environments. Their design incorporates a high-efficiency blower that allows for optimized airflow, ensuring a balanced temperature throughout the space.

The TUH2D120A9V5VA model is tailored specifically for larger applications, providing enhanced performance and increased capacity. Its dual-stage heating function guarantees consistent warmth during colder months, while the integrated energy recovery ventilator contributes to improved indoor air quality by allowing for better ventilation. This model is particularly beneficial in increasingly energy-conscious markets, demonstrating Trane's commitment to sustainability.

Both the TUH2B080A9V3VA and TUH2B080A9V4VA are designed for maximum efficiency in smaller applications. They utilize variable speed technology, allowing them to adjust the airflow according to fluctuating demand. This efficient operation not only reduces energy consumption but also minimizes noise levels, creating a more comfortable and peaceful indoor environment.

All models in the TUH2 series feature advanced diagnostics and communication capabilities, enabling remote monitoring and management of the systems. This technology helps property owners track performance and energy usage in real-time, facilitating proactive maintenance and improving overall system reliability.

Trane's TUH2 series is built with a focus on quality and innovation, utilizing high-grade materials to withstand various environmental factors. Each unit is engineered for easy installation and maintenance, ensuring that technicians can efficiently service these robust systems. In summary, the TUH2 series air handlers provide a blend of performance, efficiency, and user-friendly features, making them an excellent choice for any indoor climate control needs.