Trane TUH2C100A9V5VA, TUH2C100A9V4VA, TUH2B080A9V3VA, TUH2D120A9V5VA manual Maximum Vent Length Table

Models: TDH2B060A9V3VA TDH2B080A9V4VA TDH2B080A9V3VA TDH2D120A9V5VA TDH2C100A9V4VA TUH2B080A9V4VA TUH2D120A9V5VA TUH2B080A9V3VA TUH2C100A9V4VA TUH2C100A9V5VA

1 30
Download 30 pages 53.97 Kb
Page 20
Image 20
Maximum Vent

Maximum Vent

Length Table

VENT LENGTH TABLE

ALTITUDE

MAXIMUM TOTAL EQUIVALENT LENGTH IN FEET

 

 

FOR VENT AND INLET AIR (SEE NOTES)

 

 

 

 

 

 

 

0-7,000 Feet

2 INCH PIPE

 

2.5 INCH PIPE

 

3 or 4 INCH PIPE

 

 

 

 

 

 

*UH/DH2B060A9V3VA

200

 

200

 

200

 

 

 

 

 

 

*UH/DH2B080A9V3VA

50

 

120

 

200

*UH/DH2B080A9V4VA

 

 

 

 

 

 

 

 

 

 

 

 

 

*UH/DH2C100A9V4VA

Not Allowed

 

60

 

200

*UH2C100A9V5VA

 

 

 

 

 

 

 

 

 

 

 

 

 

*UH/DH2D120A9V5VA

Not Allowed

 

Not Allowed

 

200

 

 

 

 

 

 

7,000-9,500 Feet

2 INCH PIPE

 

2.5 INCH PIPE

 

3 or 4 INCH PIPE

 

 

 

 

 

 

*UH/DH2B060A9V3VA

100

 

100

 

100

 

 

 

 

 

 

*UH/DH2B080A9V3VA

25

 

60

 

100

*UH/DH2B080A9V4VA

 

 

 

 

 

 

 

 

 

 

 

 

 

*UH/DH2C100A9V4VA

Not Allowed

 

30

 

100

*UH2C100A9V5VA

 

 

 

 

 

 

 

 

 

 

 

 

 

*UH/DH2D120A9V5VA

Not Allowed

 

Not Allowed

 

100

 

 

 

 

 

 

9,500-12,000 Feet

2 INCH PIPE

 

2.5 INCH PIPE

 

3 or 4 INCH PIPE

 

 

 

 

 

 

*UH/DH2B060A9V3VA

50

 

50

 

50

 

 

 

 

 

 

*UH/DH2B080A9V3VA

Not Allowed

 

30

 

50

*UH/DH2B080A9V4VA

 

 

 

 

 

 

 

 

 

 

 

 

 

*UH/DH2C100A9V4VA

Not Allowed

 

Not Allowed

 

50

*UH2C100A9V5VA

 

 

 

 

 

 

 

 

 

 

 

 

 

*UH/DH2D120A9V5VA

Not Allowed

 

Not Allowed

 

50

 

 

 

 

 

 

NOTES: * - First letter may be "A" or "T"

1. Minimum vent length for all models: 3' horizontal or 3' vertical.

2. DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET (Except adapt- ers at the top of the furnace). If different inlet and vent pipe sizes are used, the vent pipe must adhere to the maximum length limit shown in the table above (See note 6 below for exception). The inlet pipe can be of a larger diameter, but never smaller than the vent pipe.

3. MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED! THE LENGTH SHOWN IS NOT A COMBINED TOTAL, IT IS THE MAXIMUM LENGTH OF EACH (Vent or Inlet air pipes).

4. One SHORT radius 90° elbow is equivalent to 10' of 3" or 4" pipe and one LONG radius elbow is equivalent to 6' of 3" or 4" pipe. One 90° elbow is equivalent to 7½' of 2½" pipe or 5' of 2" pipe. Two 45° elbows equal one 90°elbow.

5. The termination tee or bend must be included in the total number of elbows. If the BAYAIR30AVENTA termination kit is used, the equivalent length of pipe is 5 feet. BAYVENT200B equivalent length is 0 feet.

6. Pipe adapters are field supplied (except for the *UH/DH2D120 models).

7. For Canadian applications ONLY, IPEX 196006 may be used for horizontal and vertical terminations. IPEX 081216, IPEX 081218, and IPEX 081219 may only be used for horizontal vent terminations. Equivalent lengths are IPEX 196009 = 5 feet, IPEX 081216 = 11 feet, IPEX 081218 = 16 feet, and IPEX 081219 = 21 feet

20

Pub. No. 22-1814-08

Page 20
Image 20