Transition Networks CPSMC0800-100 Grounding Lugs, CPSMC08xx-100 PointSystem Chassis, chassis

Models: CPSMC0810-100 CPSMC0800-100

1 30
Download 30 pages 26.95 Kb
Page 18
Image 18
4.1.3Grounding Lugs

CPSMC08xx-100 PointSystem™ Chassis

4.1.3Grounding Lugs

The CPSMC08xx-100 comes equipped with grounding lugs, which are provided for a grounding conductor wire terminated with a two-hole,compression-type, grounding connector. The grounding wire -- which must be a copper conductor -- is not included with the chassis and must be provided by the customer/installer.

The electrical conducting path from the chassis must:

Flow via the grounding lugs to the Common Bonding Network (CBN) for telecom installations; or to an alternate approved grounding system (if required) for non-telecom installations,

Be of sufficiently low impedance to conduct fault currents likely to be imposed on the chassis, and

Enable proper operation of any over-current protection devices.

The two-hole, compression-type, grounding connector must be fastened to the grounding lugs with the enclosed, anti-rotationstar-washers and lug-nut fasteners. The required torque to the fasteners is specified by the connector’s manufacturer.

Grounding lugs

(6-32, 1/8" diam.)

 

Two-hole, compression-type

3/4-inch

grounding connector (not included)

 

spacing

Star washer (included)

 

 

Lug nuts (included)

12 AWG copper wire (not included)

chassis

To properly ground the CPSMC08xx-100 chassis:

1.Obtain one (1) properly-terminated, grounding conductor (12 AWG copper wire gauge or larger) with a two-hole, compression-type, grounding connector. Note the manufacturer's applied torque that is required for the connector.

2.Attach the grounding conductor to the chassis by placing the two-hole, compression-type connector onto the grounding lugs and fasten with appropriate lock-washers and lug-nuts at the proper torque.

3.Attach the opposite end of the properly-terminated grounding conductor to the Common Bonding Network (CBN) for telecom installations, or to an approved grounding system (if required) for non-telecom installations.

Grounding Lugs

Grounding Wire with a

 

 

 

CBN (for telecom installation)

 

 

 

two-hole, compression-type

 

 

or Earth Ground

grounding connector

 

 

 

24 hour Technical Support: 1-800-260-1312-- International: 00-1-952-941-7600

18

Page 18
Image 18
Transition Networks CPSMC0800-100, CPSMC0810-100 manual Grounding Lugs, CPSMC08xx-100 PointSystem Chassis, chassis