Section 4: Operation L

RECEPTACLES

overload the generator. See "Don't Overload

1201240Volt AC, 30 Amp, Locking Receptacle

Use a NEMA L14-30 plug with this receptacle. Connect a

4-wire cord set rated for 250VoltAC loads at 30 Amps (or greater) (Figure 5).You can use the same 4-wire cord if you plan t o run a I2OVolt load.

Cord Set

(Hot)

1

X (Hot)

I NEMA L 14-30

T f / Ground (Green)

This receptacle powers I201240Volt AC, 60 Hz,single phase loads requiring up t o 5,550 watts of power

(5.55 kW) at 23.1 Amps for I2OVolts o r 240Volts.The outlet is protected by a push-to-reset circuit breaker.

Use each receptacle t o operate 120Volt AC, single-phase, 60 Hz electrical loads requiring up t o 2,400 watts (2.4 kW) at 20 Amps of current. Use cord sets that are rated for 125 Volt AC loads at 20.Amps (or greater).

GENERATOR ADAPTER C O R D SET

The getierator is equipped with a 25'generator adapter cord set designed for a 240Volt, 30Amp grounded neutral circuit (Figure 7).The generator adapter.cord set provides a

convenient supply of emergency power into your dwelling so

-

that your generator can be operated safely outside.

120Volt AC, 20 Amp, Duplex
Receptacles-

Each duplex receptacle (Figure 6) is protected against overload by a push-to-reset circuit breaker.

The maximum load on each outlet is 2OAmps.The maximum total load on both yellow wire outlets or black wire outlets is 30 Amps.

NOTE: Follow all safety precautions when connecting any extension cord o r device t o the generator.