CDV Series Direct Vent Gas Fireplace

Termination Clearances

Termination clearances for buildings with combustible and noncombustible exteriors.

Inside CornerOutside CornerRecessed Location

 

 

 

 

B =

C

D

 

 

 

 

C

 

A =

 

 

Combustible

A

Combustible

 

 

6"(152mm)

 

E

6"(152mm)

 

V

Noncombustible

 

V

 

 

 

 

Noncombustible

2"(50mm)

 

 

 

 

 

V

2"(50mm)

 

 

B

 

 

Balcony -

 

Balcony -

 

 

 

 

with no side wall

 

with perpendicular side wall

 

 

G

H

 

V

V

G =

Combustible &

Noncombustible

Combustible &

Noncombustible

H = 24"(610mm)

12"(305mm)

J = 20"(508mm)

 

J

C = Maximum depth of 48" (1219mm) for recessed location.

D = Minimum width for back wall of a recessed location. Combustible 38"(965mm) Noncombustible 24"(610mm)

E = Clearance from corner in recessed location. Combustible 6"(152mm) Noncombustible 2"(50mm)

584-15

Fig. 8 Termination clearances.

General Information Assembling Vent Pipes

Canadian Installations:

Venting system must be installed in accordance with the current CSA-B149.1 installation code.

USA Installations:

The venting system must conform with local codes and/ or the current National Fuel Gas code ANSI Z223.1/ NFPA 54.

Only venting components manufactured by CFM Corpo- ration can be used in Direct Vent systems.

Flex Vent Pipes

Before joining the flex vent pipe to the unit, apply a bead of high temperature sealant* (provided) to the 4” pipe exiting the fireplace. Secure flex vent pipe in place with a hose clamp (provided).

*Be sure the flex pipe overlaps at least 1” (25 mm) onto the collars of the fireplace and termination. If the ter- mination has an internal bead, be sure to overlap and secure 1” (25 mm) past the bead.

*Be sure the vent is actually crushed before proceed- ing. Apply a tug to be sure the vent will not slip off the collars.

Repeat process with 7” flex vent pipe. The same proce- dure must be performed on the vent side.

Hose Clamp

Apply High Tempera- ture Sealant

FP1471a

Fig. 9 Apply high temperature sealant to 4” and 7” pipes.