Vermont Casting DBR36, DBR39, DBR33 installation instructions Vertical Thru The Roof Installation

Models: DBR36 DBR33 DBR39

1 32
Download 32 pages 15.6 Kb
Page 17
Image 17
VERTICAL THRU THE ROOF INSTALLATION

 

MAX.

 

8 FEET

 

2438mm

45°

 

 

40 FEET

MAX.

(12.2m)

8 FEET

 

2438mm

 

 

45°

TYPICAL OFFSET INSTALLATION

 

Fig. 34

TYPICAL 7DVCS

APPLICATION

Fig. 35

TYPICAL ROOF

SUPPORT

APPLICATION

Fig. 36

VERTICAL THRU THE ROOF INSTALLATION

1.Locate your fireplace.

2.Plumb to centre of the (4") 90º transition elbow (7DVRT90) from ceiling above and mark position.

3.Cut opening equal to 9-3/8" x 9-3/8" (240 mm x 240 mm).

4.Proceed to plumb for additional openings through the roof. In all cases, the opening must provide a minimum of 1 inch clearance to the vent pipe, i.e., the hole must be a minimum of 9-3/8" x 9-3/8" (240 mm x 240 mm).

5.Place firestop(s) #7DVFS into position and secure. (Fig. 38)

6.Install roof support (Fig. 35) and roof flashing making sure upper flange of flashing is below the shingles. (Fig. 39)

7.Install appropriate pipe sections until above the flash- ing. (See Fig. 39 for #'s 7, 8 and 9).

8.Install storm collar and seal around the pipe.

9.Add additional vent lengths for proper height.

10.Apply high temperature sealant to 4" and 7" collars of vent termination and install.

Attic

 

Insulation

 

Shield

11"

 

VENT TERMINATION

 

 

STORM COLLAR

 

ROOF

ROOF FLASHING

 

2' Min.

 

 

 

 

ROOF SUPPORT

 

ATTIC INSULATION

 

 

CEILING JOISTS

 

JOISTS

 

40 FEET

ATTIC INSULATION

 

(12.2m)

 

SHIELD

 

 

TYPICAL STRAIGHT-UP INSTALLATION

Fig. 37

 

 

Clearance above a roof shall extend a mini- mum of 24" (610mm) above the highest point when it passes through the roof surface, and any other obstruciton within a horizontal distance of 18" (450mm).

- 17 -

 

 

JOIST

Ceiling

11"

UPPER FLOOR

Installation

 

 

 

 

 

JOIST

Manual background FIRESTOP

SPACER

NAILS (4)

Fig. 38

Fig. 38 If there is a room above ceiling level, firestop spacer must be installed on both the bottom and the top side of the ceiling joists. If an attic is above ceiling level a 7DVAIS (Attic Insulation Shield) must be installed.

Fig. 39. The enlarged ends of the vent section always face downward.

SHEETMETAL Manual background SCREWS (#5) —

3 PER JOINT

Manual background SEALANT

STORM

COLLAR

Fig. 39

Page 17
Image 17
Vermont Casting DBR36, DBR39, DBR33 installation instructions Vertical Thru The Roof Installation