DVBR Series Direct Vent Gas Fireplace
Locating Your Fireplace
E | A | B |
Y |
| |
|
| |
| C | X |
|
| |
D |
|
|
Y |
| B |
|
| |
| F |
|
|
| |
Fig. 1 Locating Gas Fireplace |
|
A) Flat on wall | B) Cross corner | C) **Island |
D) *Room divider | E) *Flat on wall corner | F) Chase installation |
Y) 6” minimum |
|
|
Note (Fig. 1):
**Island (C) and Room Divider (D) installation is possible as long as the horizontal portion of the vent system (X) does not exceed 20’ (610 cm). See details in Venting Section.
* When you install your fireplace in(D) Room divider or (E) Flat on wall corner positions (Y), a minimum of 0” (0mm) clearance must be maintained from the perpendicular wall and the front of the fireplace.
Clearance to Combustibles
Appliance |
|
Top | 0” (0 mm) |
Bottom | 0” (0 mm) |
Side | 0” (0 mm) |
Back | 0” (0 mm) |
Perpendicular Sidewall | 0” (0 mm) |
Top of unit to ceiling | 36” (914 mm) |
Front of unit to combustibles | 36” (914 mm) |
Venting |
|
Concentric sections of DV Vent | 1” (25 mm) |
Nonconcentric sections of DV Vent |
|
Sides and bottom | 1” (25 mm) |
Top | 2” (51 mm) |
Mantels
The height that a combustible mantel is fitted above the fireplace is dependent on the depth of the mantel. This also applies to the distance between the mantel leg (if fitted) and the fireplace.
For the correct mounting height and widths, refer to Figures 4a and 4b and the Mantel Chart below.
The distances and reference points are not affected by the fitting of a bay window front trim kit.
Noncombustible mantels and legs may be installed at any height and width around the appliance. When using paint or lacquer, it must be heat resistant to prevent discoloration.
6
V
W
X
Y
Z
A B C D E
Fireplace
|
|
|
|
| Top of Combustion | ||
|
|
|
|
| Chamber | ||
|
|
|
|
|
|
| CFM146a |
Bottom of Door Trim |
|
|
|
| |||
|
|
|
|
| |||
|
| Mantel Chart |
| ||||
|
| Mantel |
|
| Mantel from Top | ||
Ref. | Shelf Depth |
| Ref. | of Comb. Chamber | |||
V | 14” | (356 mm) |
| A | 18” | (457 mm) | |
W | 12” | (305 mm) |
| B | 16” | (406 mm) | |
X | 10” | (254 mm) |
| C | 14” | (356 mm) | |
Y | 8” | (203 mm) |
| D | 12” | (305 mm) | |
Z | 1¹⁄₂” | (38 mm) |
| E | 8” | (203 mm) |
Fig. 4a Combustible mantel minimum installation.
|
|
|
|
| J | I H |
|
Black |
|
|
|
| G | ||
|
|
|
|
| |||
Surround Face |
| Mantel |
|
|
| ||
|
|
|
|
|
|
| |
CFM164a |
|
|
| Leg |
|
|
|
Side of |
|
| MLK |
|
|
| |
Combustion Chamber |
| N |
|
|
| ||
| O |
|
|
| |||
|
|
|
|
|
|
| |
|
|
|
|
|
|
| CFM170 |
| Mantel Leg |
| Mantel Leg from Side | ||||
Ref. |
| Depth | Ref. | of Combusion Opening | |||
F | 14” | (356 mm) | K | 14” | (356 mm) | ||
G | 12” | (305 mm) | L | 12” | (305 mm) | ||
H | 10” | (254 mm) | M | 10” | (254 mm) | ||
I | 8” | (203 mm) | N | 8” | (203 mm) | ||
J | 4” | (102 mm) | O | 3¹⁄₂” | (89 mm) | ||
Fig. 4b | Combustible mantel minimum installation. |
| |||||
|
|
|
|
|
| 20000584 |