Passing Through a

Combustible Wall or Ceiling

An approved pass-through device is always required when a vent passes through a combustible wall or ceil- ing. Check with the maker of the vent system for the correct listed devices that are available. A listed pass- through device is required whether or not the installa- tion includes decorative pipe around the Type B venting system. NOTE: It is essential to seal between the ceil- ing support (sometimes called a ‘firestop spacer’) and the decorative pipe, if installed, with a high-temperature silicone sealant. (Fig. 6)

Complete the venting system installation according to the manufacturer’s instructions.

Air Space as Re-

Joists

quired by Code

 

 

Ceiling

 

Support

High-tempera-

 

ture Silicone

Trim Col-

Sealant

lar

 

Decorative

High-tem-

6” Pipe

perature

 

Silicone

 

Sealant

Listed 4”

(102 mm)Air Space

ST361 B-Vent

Fig. 6 A ceiling pass-through, with decorative pipe around the vent.

Stardance Natural Vent Gas Heater

Venting Requirements

 

elbow)

36

 

 

 

 

 

 

 

34

 

 

A

 

 

 

 

32

 

 

B

 

 

 

30

 

 

 

 

 

 

any

 

 

 

 

 

 

28

 

 

 

 

 

 

feet) before

 

 

 

 

 

 

26

 

 

 

 

 

 

24

 

 

 

 

 

 

 

 

 

 

 

 

 

(in unit

22

 

 

 

 

 

 

20

 

 

 

 

 

 

Vertical Run

from top of the

 

 

 

 

 

 

18

 

 

 

 

 

 

16

 

 

 

 

 

 

14

 

 

 

 

 

 

12

 

 

 

 

 

 

10

 

 

 

 

 

 

 

(Measured

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

1

2

4

6

8

10 12 14 16 18

20 22 24

Horizontal Run (in feet)

Venting Runs

NOTE: When venting staight vertical, without an elbow, a minimum of 8 ft. vertical is required off the top of the stove.

= Acceptable venting configuration = Unacceptable venting configuration

A:Vertical installations up to 36 feet (12m) in height. Up to an 18 ft. horizontal vent run can be installed within the vent system using a maximum of two 90-degree elbows or four 45-degree elbows.

B:Vertical installations up to 36 feet (12m) in height. Up to a 24 ft. horizontal vent run can be installed within the vent system using a

maximum of two 45-degree elbows.

 

(Ratio = 2/3, Hor./Vert.)

FP567b

Fig. 7 Vent termination window.

20007067

Page 7
Image 7
Vermont Casting SNV30 manual Passing Through a Combustible Wall or Ceiling, Venting Requirements