CONTROL BOARD SETUP
Viking Heater
The operator has an integrated heater that is thermostatically controlled. Activate this feature when the operator is used in application temperatures down to
To set the heater to turn on at the Close Limit:
1.Use the “Diagnose” button to scroll through the LCD Display to “HEATER CLS”
2.Press and hold the “Stop” button on the control board.
3.Press and release the “Diagnose” button to turn this feature ON and OFF.
To set the heater to turn on at the Open Limit:
1.Use the “Diagnose” button to scroll through the LCD Display to “HEATER OPN”
2.Perform steps
HEATER CLS ON
HEATER OPN ON
NOTE: If the application requires the gate to be held open for any reason, set the HEATER ON for both limit positions.
!IMPORTANT: A POSITIVE STOP must be used on the gate at the limit position(s) the HEATER has been set for.
Viking Lock Mode
Turning this feature ON will secure the gate at the closed position, preventing unauthorized manual entry.
Use the LCD Display to activate this feature.
1.Use the “Diagnose” button to scroll through the LCD menu to “LOCK MOD”
2.Press and hold the “Stop” button on the control board.
3.Press and release the “Diagnose” button to turn this feature ON and OFF.
LOCK MOD ON