LOCATION — ELECTRIC STEAMERS & STEAM GENERATORS
Position the steamer or steam generator in its final location.
The recommended clearance for proper operation is 36" (91.4 cm) at the front. The required clearance from combustible or
An exhaust system should be located directly above the steamer to exhaust steam and heat generated by the steamer.
IMPORTANT: Do not locate the boiler base directly over a drain.
ELECTRICAL CONNECTIONS — ELECTRIC STEAMERS & STEAM GENERATORS
WARNING: ELECTRICAL AND GROUNDING CONNECTIONS MUST COMPLY WITH THE APPLICABLE PORTIONS OF THE NATIONAL ELECTRICAL CODE AND/OR OTHER LOCAL ELECTRICAL CODES.
WARNING: DISCONNECT THE ELECTRICAL POWER TO THE MACHINE AND FOLLOW LOCKOUT / TAGOUT PROCEDURES.
Connect the electrical supply circuit to the terminal block in the field connection box located behind the left side panel at the rear. A 17/8" (4.8 cm) diameter hole for 11/2" (3.8 cm)
The wiring diagram is located on the door of the boiler.
ELECTRICAL DATA
|
|
|
|
| Minimum Circuit Ampacity |
Volts | Hertz | Phase | Total KW | Machine Amps | Maximum Protective Device |
|
|
|
|
| AMPS |
208 | 60 | 1 | 24 | 115.4 | 150 |
|
|
| 24 | 66.6 | 90 |
208 | 60 | 3 | 36 | 99.9 | 125 |
|
|
| 42 | 116.6 | 150 |
240 | 60 | 1 | 24 | 100 | 125 |
|
|
| 24 | 57.7 | 90 |
240 | 60 | 3 | 36 | 86.6 | 125 |
|
|
| 48 | 115.5 | 150 |
|
|
| 24 | 28.9 | 50 |
480 | 60 | 3 | 36 | 43.3 | 70 |
|
|
| 48 | 57.7 | 90 |
|
|
|
|
|
|
Compiled in accordance with the National Electrical Code,