Manual • Installation •
B1 |
| gas | |
| |||
Install system water piping (space heating) | |||
| |||
|
System water piping methods
Figure 11 Expansion tank piping
All piping methods shown in this manual use primary/secondary connection to the boiler loop. These designs ensure proper
flow through the Gas boiler, for the most efficient and reliable operation of the boiler and the heating system. For other piping methods, consult your local
separate Gas boiler piping guides.
Expansion tank and make-up water
1.Ensure expansion tank size will handle boiler and system water volume and temperature. Allow 3 gallons for the boiler and its piping.
Undersized expansion tanks cause system water to be lost from relief valve and
2.Tank must be located as shown in this supplement, or following recognized design methods. See tank manufacturer’s instructions for details.
3.Connect the expansion tank to the air separator only if the separator is on the suction side of the system circulator. Always install the system fill con- nection at the same point as the expansion tank connection to the system.
4.The piping drawings in this manual show only diaphragm expansion tanks. Use only
5.Refer to the Boiler Manual for other system piping examples.
Diaphragm (or bladder) expansion tank
1.Always install an automatic air vent on top of the air separator to remove residual air from the system.
2.See Figure 11 for correct location of the expansion tank.
DO NOT USE a closed-type expansion tank
The
Boiler circulator
The boiler circulator is shipped loose. It must be located in either the return or supply piping, as shown in the appropriate piping diagram in this supplement or the Boiler Manual.
DO NOT use the boiler circulator in any location other than those shown in this manual or the boiler manual. The boiler circulator is selected to ensure adequate
flow through the boiler. Failure to comply could result in unreliable per- formance and nuisance shutdowns from insufficient flow.
Sizing space heat system piping
1.See Figures 12 and 13, pages 26 and 27, or the Gas Boiler Manual for recommended piping. In all diagrams, the space heating system is isolated from the boiler loop by the primary/secondary connec- tion.
2.Size the piping and components in the space heating
Part Number | 25 |