Manual • Installation •
A1 Pre-installation continued
Operating • Maximum domestic hot water temperature (Use only for special
restrictions | operational requirements): |
| |
• 160°F for GOLD Plus 30/40/60/80 or | Plus 40/60/80. | ||
| |||
| • 190°F for PLUS 100/110/119. |
|
• Maximum boiler water temperature — 210°F.
• Maximum working pressure for inner (domestic water) tank — 150 psig.
• Maximum working pressure for outer (boiler water) tank — 45 psig.
• pH and chloride limits for water heaters are:
• chloride — less than 80 mg/l.
• pH — above 6 and less than 8.
Code restrictions National Standard Plumbing Code
Single wall heat exchanger in water heater complies with National Standard Plumbing Code, provided that:
•boiler water (including additives) is practically
•boiler water pressure is limited to maximum 30 psig by approved relief valve.
Uniform Plumbing Code
1.The heat transfer medium is potable water or contains only substances which are recognized as safe by the U. S. Food and Drug Administration.
2.The pressure of the heat transfer medium is maintained less than the normal minimum operating pressure of the potable water system.
Exception: Steam complying with #1, above.
3.The equipment is permanently labeled to indicate that only additives recognized as safe by the FDA shall be used in the heat transfer medium.
Other heat exchanger designs may be permitted where approved by the Administrative
Authority.
Part Number |