Weil-McLain PLUS-E017-A/1206 manual Water heater piping, Temperature & pressure T & P relief valve

Models: PLUS-E017-A/1206

1 68
Download 68 pages 54.62 Kb
Page 8
Image 8
Temperature & pressure (T & P) relief valve

PLUS LINEIndirect-Fired Water Heaters – Series 3

A2

Temperature & pressure (T & P) relief valve

Water heater piping

To reduce risk of excessive pressures and temperatures in water heater, install temperature and pressure protective equipment required by local codes, but no less than a combination temperature and pressure relief valve certified by a nationally recognized testing laboratory that main- tains periodic inspection of production of listed equipment or materials, as meeting the requirements for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22. This valve must be marked with a maximum working pressure of the water heater.

1.Size T&P relief valve by the following specifications, unless they conflict with local codes:

GOLD Plus 30/40/60/80 or Water heater pipingAir ventManual background Plus 40/60/80: 3/4” NPT with an AGA Rating of 100,000 BTU/hr, with a long element. Set to relieve at 150 psi. (Watts model 100XL-8 relief valve or equivalent.)

PLUS 100/110/119: 3/4” NPT with an AGA Rating of 200,000 BTU/hr, with a long element. Set to relieve at 150 psi. (Watts model 40XL-8 relief valve or equivalent.)

GOLD Plus, Manual backgroundManual backgroundManual background Plus and PLUS water heaters are exempt from ASME Section VIII per Interpretation VIII-1-86-136. Consult local codes for applicability.

2.Installing T&P relief valve –

GOLD Plus 30/40/60/80 or Manual backgroundManual backgroundManual background Plus 40/60/80 (Page 9)

Install T&P relief valve either:

a.in tapping marked AUX.

b.in run (straight through leg) of tee located at domestic hot water outlet of water heater. (Required for the Commonwealth of Massachusetts.) Use a long element T&P relief valve.

PLUS 100/110/119 (Page 11)

Install T&P relief valve either:

a.in tapping marked AUX.

b.in run (straight through leg) of tee located at domestic hot water outlet of water heater. (Required for the Commonwealth of Massachusetts.) Use a long element T&P relief valve.

3.T&P relief valve discharge piping must be:

made of material serviceable for temperatures of 250°F or greater.

directed so that hot water flows away from all persons.

directed to a suitable place for disposal.

installed so as to allow complete draining of the T&P relief valve and discharge line.

T&P relief valve discharge piping must not be:

excessively long. Using more than 2 elbows or 15 feet of piping can reduce discharge capacity.

directly connected to a drain. Terminate discharge piping within 6” from floor. Refer to local codes.

plugged, reduced or restricted.

Do not install any valve between T&P relief valve and tank connection, or on T&P relief valve discharge piping. Do not plug T&P relief valve or discharge piping. Improper placement and piping of T&P relief valve can cause severe personal injury, death or substantial property damage.

Air vent

The boiler-side piping must be equipped with a diaphragm- or bladder-

 

 

type expansion tank, NOT a closed-type expansion tank.

1.Remove plastic shipping cap from 1/2” NPT pipe fitting on top of water heater.

2.Install automatic air vent provided with water heater, using suitable pipe dope or tape.

3.Unscrew vent cap on air vent one full turn. Leave cap unscrewed one turn for normal venting.

Part Number PLUS-E017-A/1206

Page 8
Image 8
Weil-McLain PLUS-E017-A/1206 manual Water heater piping, Temperature & pressure T & P relief valve, Air vent