C Boiler-side piping (except Manual backgroundManual backgroundManual background Gas)continued

Figure 29

Steam boiler application

Domestic water heating using water pumped from steam boiler

Locate flow/check valve as close as possible to water heater boiler side connections

— to reduce heat loss between cycles.

Use ball valve 7 to blend some of the water returning to the boiler with the hot water coming from the boiler. This will reduce the possibil- ity of flashing (cavitation) in the circulator. Slowly open valve 7 until temperature gauge 8 reads 200°F.

Lock or remove the handle from valve 7 after adjusting.

Notes

1.

These drawings are conceptual only. They show representative piping components and

 

 

layout. Weil-McLain does not represent that the drawings meet any particular mechanical

 

 

or building codes. The installer is responsible for inclusion of all required safety devices, or

 

 

other miscellaneous piping hardware not shown on drawings. The installer is responsible

 

 

for proper sizing/selection of all hardware shown on this diagram.

 