OPERATIONAL MODES
There are four main operational modes for the | During the Freeze mode, some of the hot gas | |
ice maker (more detailed operation is found in | that is in the condenser accumulating tube, | |
the flow chart on page | condenses to a liquid, and remains in the ac- | |
• Freeze | cumulating tube. | |
During the later stages of the Freeze mode, as | ||
• Harvest | ||
• Clean | the ice slab forms on the evaporator freezing | |
plate, some of the refrigerant passing through | ||
• Service (Diagnostics) | ||
the evaporator will not evaporate into a gas, but | ||
ICE MAKING CYCLE | ||
will remain a liquid. This liquid refrigerant will | ||
In addition, there are three possible “Off” cycles | settle in the accumulator, while the refrigerant | |
for the ice maker. They occur when: | vapor is sucked off through the suction tube at | |
1. The bin is full of ice and the LED is il- | the top of the accumulator. This accumulated | |
liquid refrigerant will eventually be directed to | ||
luminated “ON/OFF” (Idle mode). | ||
the evaporator to quickly warm the evaporator | ||
2. The "On/OFF” control switch has been | ||
plate during the Harvest mode. | ||
held for three seconds. The ON/OFF | ||
NOTE: It is very important that the accumulator | ||
LED will go out. | ||
is not tilted out of a horizontal position. If moved, | ||
3. The Holiday Mode. | ||
it could cause compressor failure. | ||
Electrical System | ||
Water System | ||
Line Voltage is supplied to the electrical control | ||
The water recirculating pump moves the water | ||
switches and the primary side of the | ||
from the reservoir pan up to the distributor, | ||
dual transformer. The dual transformer reduces | ||
where it flows out over the evaporator freez- | ||
120 VAC to 8.75 VAC for the cutter grid and | ||
ing plate. | ||
the bin light and 12 VAC for the drain and recir- | ||
Water that does not freeze on the evaporator | ||
culating pumps. The electronic control board | ||
directs 12 VAC to the water recirculating and | plate runs off the front edge, and falls back into | |
reservoir drain pumps, and 120 VAC to the | the reservoir, where it is recirculated back to | |
hot gas solenoid, condenser fan motor, and | the water distributor. | |
compressor. The measured fill water valve will | As the ice slab forms, the minerals in the water | |
always have 120 VAC on the BK and WH wires | are on the surface of the ice. The water flow- | |
and 14 VDC on the OR/WH and BK/RD wires. | ing over the top of the ice slab washes these | |
An evaporator thermistor supplies temperature | minerals back into the water reservoir pan. The | |
information to the electronic control to determine | water continues to recirculate until the water | |
when to terminate the harvest cycle. | level in the reservoir drops to the bottom of the | |
Refrigeration System | water level sensor. When the water level in the | |
reservoir drops below the sensor, the control | ||
The hot gas refrigerant, under high pressure, is | ||
terminates the freeze mode and initiates the | ||
forced through the condenser, where it changes | harvest mode. | |
into a liquid, and flows through the drier and | The control signals the measured fill valve to fill | |
capillary tube into the evaporator. Under low | ||
to the selected water level setting. The mea- | ||
pressure in the evaporator, the liquid refrigerant | ||
sured fill valve uses a flow meter to accurately fill | ||
absorbs heat from the water flowing over the | ||
to the correct volume. Thin Ice uses 32 ounces | ||
evaporator as the refrigerant evaporates into | ||
(954cc), Normal Ice 37 ounces (1106cc), and | ||
a gas. As a low pressure gas, the refrigerant | ||
Thick Ice 42.5 ounces (1258cc). | ||
flows back through the suction line of the heat | ||
| ||
exchanger, to the compressor. |
|