Xantrex Technology 3000 manual Connecting the DC Cables, To make the DC connections

Models: 3000

1 64
Download 64 pages 49.86 Kb
Page 31
Image 31

Connecting the DC Cables

Connecting the DC Cables

Do not remove the terminal nut

Do not place anything between battery cable lug and terminal surface. Assemble exactly as shown.

Copper Compression Lug

Aluminum Box Lug

Figure 3-5DC cable lug examples

Consult Figure 3-1, “Configuration for Normal Loads” on page 3–2, or Figure 3-2, “Configuration for Heavy Loads” on page 3–2 for additional details that are specific to your installation.

To make the DC connections:

1.Cut the cables to the correct length with enough insulation stripped off so you can properly install the type of terminals you will be using.

The terminals on the DC end are designed to fit up to 500 MCM crimp-on ring terminals (either AMP or ILSCO) or box connectors.

2.Attach the connectors to both cables.

If using compression lugs, attach the terminals to both cables using the crimp tool recommended by the manufacturer of the ring terminals. There must be no stray wire strands protruding from the terminal. If using box lugs, attach the lug to the XPower Inverter 3000 Plus first, then insert the wire and tighten the set screw to the torque recommended by the lug manufacturer.

3.Route the DC supply cables from the battery bank to the inverter.

975-0128-01-01

3–13

Page 31
Image 31
Xantrex Technology 3000 manual Connecting the DC Cables, To make the DC connections