Wiring the Inverter

Chapter 3 provides information about DC and AC wiring, and grounding the GT Inverter and the PV array.

This chapter does not provide sufficient information for anyone but a qualified installer to install this product. Installers should be electricians or technicians fully educated on the hazards of installing electrical equipment.

Grounding Requirements

AC Grounding

The GT Inverter must be connected to the AC ground from the utility via the GT

 

Inverter ground bar.

PV Grounding

The PV array (frame) ground should be connected to the GT Inverter ground bar.

 

The size for the conductor is usually based on the size of the largest conductor in

 

the DC system.

 

A DC grounding electrode conductor may be required by the Authority Having

 

Jurisdiction (AHJ). Use the GT Inverter ground bar for this connection (see

 

Figure 3-2 on page 3–3).

CAUTION: Equipment damage

Provide adequate clearance for grounding wires inside the GT Inverter wiring box. Ensure that the bare copper grounding wire is more than ½ inch clear of the DC/AC interconnect circuit board.

Two ¼-inch (7 mm) knockouts in the bottom of the wiring box are intended for routing the ground conductors to the ground bar. See Figure 3-1.