Input
Input voltage, Maximum Power Point range | 240 to 550 Vdc |
Absolute maximum array open circuit voltage | 600 Vdc |
Maximum input current | 22.0 Adc |
Maximum array short circuit current | 24 Adc |
Reverse polarity protection | Short circuit diode |
Ground fault protection | GF detection, IDIF > 1 A |
Output
Maximum output power | 5000 W AC | |
Nominal output voltage | 240 V | |
|
| |
Operating range, utility voltage* | 211 to 264 Vac | |
|
|
|
Nominal output frequency | 60 | Hz |
|
| |
Operating range, utility frequency* | 59.3 to 60.5 Hz | |
|
| |
Startup current | 0 Aac | |
|
|
|
Maximum continuous output current | 21 | A |
|
|
|
Output overcurrent protection | 30 | A RMS |
|
| |
Maximum utility backfeed current | 0 A | |
|
| |
Total Harmonic Distortion | <5% | |
|
| |
Power factor | >0.95% | |
|
| |
Utility monitoring— islanding protection | Vac, fac as per UL 1741 (2005) | |
|
| |
Output characteristics | Current source | |
|
| |
Output current waveform | Sine wave | |
|
|
|
*Factory settings can be adjusted with the approval of the utility. This unit is provided with adjustable trip limits and may be aggregated above 30 kW on a single Point of Common Coupling. See “Adjustable Voltage, Frequency and Reconnection Settings” on page