Wiring the Inverter

Ground bar

Knockouts for ground conductors

Figure 3-1Ground Conductor Knockouts

The ground bar accepts wires up to #4 AWG. Torque ground wires as specified in Table 3-1.

Table 3-1Torque Values for Ground Wiring

Wire Size

 

Torque Value

AWG

mm2

in-lb

Nm

14–10

2.5–6.0

25–35

3.0–4.0

8

10

30–40

3.4–4.5

6–4

16–25

35–45

4.0–5.0

Important: In most models, the negative PV conductor is internally bonded to the ground system within the inverter’s ground fault detection circuit. Inverter models marked with the “-POS” suffix are positive grounded and have the positive PV conductor internally bonded to the ground system through the inverter’s ground fault protection circuit. It is important that the negative (or positive) PV conductor is not bonded to the ground at any other point in the system.