| Communications Wiring for Multiple Inverters |
|
|
Terminators | The male network terminator supplied with each GT Inverter (Figure |
| required at each end of the network to ensure the communication signal quality on |
| the network. |
| Figure | Male Network Terminator | |
GT Inverter Xanbus | Two RJ45 ports are provided in the GT Inverter, accessible from the wiring box. | ||
Ports | See Figure | ||
| RJ11 ports | RJ45 | |
| (not used) | Xanbus ports | See page |
Male network terminator
Figure
Cabling Requirements
CAUTION: Equipment damage
Do not use crossover cable in a Xanbus system.
The network uses Category 5 (CAT 5 or CAT5e) cable, a standard cable available from any computer supply store. The cable consists of eight conductors in four twisted pairs with an RJ45 modular connector wired to the T568A standard. Table