| Mechanical Specifications | |
|
|
|
|
|
Display Accuracy |
|
|
| |
| Instantaneous Power |
| +/- (30 W + 1% of reading) | |
| ||||
| Voltage |
| +/- (1% of rating + 1% of reading) |
|
| Current |
| +/- (1% of rating + 1% of reading) |
|
| System Lifetime energy |
| +/- 5% |
|
|
|
|
|
|
Mechanical Specifications
Outdoor enclosure | NEMA 3R, Rainproof |
Inverter dimensions | 28.5 × 15.9 × 5.7 inches (72.4 × 40.3 × 14.5 cm) |
(H × W × D) |
|
Shipping dimensions | 34.1 × 20.4 × 10.3 inches (86.6 × 51.8 × 26.2 cm) |
(H × W × D) |
|
Inverter weight | 58 lb (26.3 kg) |
Shipping weight | 76 lb (34.5 kg) |
Input and output | AC and DC terminals accept wire sizes of 2.5 to 16 mm2 |
terminals | (#14 to #6 AWG) |
Disconnect switch | Integrated switch, disconnects both AC and DC |
| (meets NEC article 690), rated @ 600 Vdc |
|
|
Regulatory Approvals
The GT Inverter has complete
•UL 1741 1st Edition 2005 Revision – Standard for Inverters, Converters, Controllers and Interconnection System Equipment for Use with Distributed Energy Resources (Includes IEEE 1547 and 1547.1)
•CSA C22.2 No.
•IEEE C62.41.2 – IEEE Recommended Practice on the Characterization of surges in
Note: This inverter is compliant with IEEE 1547 for those requirements referenced in UL1741 (2005), section 46.1.1.:
A utility interactive inverter and interconnection system equipment (ISE) shall comply with the Standard for Interconnecting Distributed Resources With Electric Power Systems, IEEE 1547, and the Standard for Cofnformance Test Procedures for Equipment Interconnecting Distributed Resources with Electric Power Systems, IEEE 1547.1, excluding the requirements for Interconnection Installation Evaluation, Commissioning Tests, and Periodic Interconnection Tests.