DC and AC Wiring for Multiple Inverters
DC and AC Wiring for Multiple Inverters
DC and AC wiring for multiple inverters is illustrated in Figure
If there will be more than one PV array, label the positive and negative wire pairs appropriately (for example: PV1 POS, PV1 NEG, PV1 GND, PV2 POS, etc.).
If required by the AHJ, a DC grounding conductor may be connected to each inverter’s ground bar. One inverter will connect to a common grounding conductor. The other inverters will use tap connectors. Connection is then made to the DC or AC grounding electrode as per NEC 690.47.
Ensure all connections are correctly wired and properly torqued to a maximum 16
PV Array #2 (PV2)
+ | + |
|
– | – | PV Array #1 (PV1) |
Utility Meter
L1 L2 N G
L1 L2 N G
L 1 | L 2 |
Neutral
L1
L2
L1
L2
Ground
Main Utility Service Panel
Grounding not shown.
Figure