Installing the TS400

DC Cables

For the best load starting performance, the DC cables should be as short and large as possible. See Table 2-1for minimum recommended cable size. Using a smaller cable may cause the inverter to shut down under heavy load. A larger cable may be used.

Table 2-1Minimum Recommended DC Input Cable (copper) — AWG

&DEOH￿/HQJWK￿￿%DWWHU\￿WR￿,QYHUWHU

0LQLPXP￿5HFRPPHQGHG￿

￿HDFK￿FDEOH￿

&DEOH￿6L]H￿³￿$:*

 

 

0–10 feet (0–3 meters)

No. 6

 

 

10–15 feet (3–4.5 meters)

No. 4

 

 

15–30 feet (4.5–9 meters)

No. 2

 

 

30–40 feet (9–12 meters)

No. 0

 

 

DC Fuse and Disconnect or DC Circuit Breaker

If you are using a DC fuse and Disconnect, a maximum 80 amp Class T fuse shall be used for the DC fuse. A fuse of lower rating can be used, but it shall not be lower than 60 amp Class T. The Disconnect shall be rated at least 50 amps.

Additionally, a DC circuit breaker rated 50 amps can be used.