Designing Your Installation

Choosing an Appropriate Location

WARNING: Explosion or fire hazard

The XM 1800 contains components that may produce arcs or sparks. To prevent fire or explosion, do not install the inverter in compartments containing batteries or flammable materials, or in locations that require Ignition-Protected equipment such as areas containing gasoline engines, tanks, or fuel-line fittings.

WARNING: Fire hazard

To reduce the risk of fire, do not cover or obstruct the ventilation openings. Do not install the XM 1800 in a zero-clearance compartment. Overheating may result.

The XM 1800 must only be installed in a location that is:

:

Dry

Do not allow water or other liquids to drip or splash on it.

Cool

Ambient air temperature should be between 32 ºF and

 

105 ºF (0 ºC and 40 ºC)—the cooler the better within this

 

range.

Ventilated

Allow at least 3 inches (7.5 cm) of clearance around the

 

inverter for air flow. Ensure that the ventilation openings on

 

the DC end of the unit are not obstructed.

Safe

Do not install the inverter in the same compartment as

 

batteries or in any compartment capable of storing

 

flammable liquids like gasoline.

Close to

Do not use excessive DC cable lengths. DC cable wire

battery

resistance and the resulting voltage drop reduces input

 

power. Voltage drop in AC wires is of less critical

 

importance because resistance in wire carrying AC current

 

is less. AC wires are also less expensive. In general, longer

 

AC wires are preferable to longer DC cables.

Protected from

Do not mount the inverter where it will be exposed to gases

battery gases

produced by batteries. Battery gases are corrosive, and

 

prolonged exposure to battery gases will damage the

 

inverter.

975-0263-01-01

3–5

Page 24
Image 24
Xantrex Technology XM 1000 manual Choosing an Appropriate Location, XM 1800 must only be installed in a location that is