Installation

A separate screw is provided to connect the AC input ground (see

Figure 3-5 on page 3–16).

AC output ground screw

AC knockout

STATUS

 

 

 

Utility

 

Input Voltage (V)

 

Battery

Select

Input Current (A)

 

 

 

Fault

 

Output Power (W)

XM1000

 

 

GND

 

 

 

 

GND

AC

N

L

N

L

AC

OUT

IN

CAUTION! Do not connect the AC OUT to any other source of power. Damage to unit may occur.

AC input ground screw

AC knockout

Figure 3-5XM 1800 AC Wiring Compartment

8.Strip about 2 inches (50 mm) from the jacket of the AC input cable.

The AC input cable may be either solid or stranded, but must have three conductors and be sized as in Table 3-3 on page 3–14. (The AC terminal block accepts wire sizes up to No. 10 AWG.)

9.Strip approximately 3/8 inch (10 mm) off the insulation of each conductor.

10.Run the AC cable through the right-hand side strain-relief clamp and into the wiring compartment.

11.Fasten the Ground wire to the grounding screw.

12.Using the 1/8 inch slot screwdriver, loosen the wire attachment screws on the terminals.

CAUTION: Reverse polarity

Improper connections (connecting a line conductor to a neutral conductor, for example) will cause the XM 1800 to malfunction and may permanently damage the inverter. Damage caused by a reverse polarity connection is not covered by your warranty.

13.Insert the Line and Neutral wires into the corresponding terminals.

14.Tighten the wire attachment screws to a torque of 1.3–1.8 lbf-ft (1.76–2.44 Nm). Leave some wiring slack inside the wiring compartment.