Xantrex Technology XM 1000, XM 1800 manual Testing Your Installation, Testing in Invert Mode

Models: XM 1800 XM 1000

1 81
Download 81 pages 18.09 Kb
Page 43
Image 43

Installation

14.Install the lock washer and nut that are supplied. Tighten the nut to a torque of 108–120 in-lbf (12.2–13.6 N-m). Make the connection snug enough so the ring terminal does not move around on the DC terminal, but do not overtighten.

15.Slip the DC terminal covers over the XM 1800 DC terminals.

16.Use the disconnect/battery selector switch to select one of the batteries or battery banks (the house bank is preferred over the start bank).

Testing Your Installation

WARNING: Shock hazard

The on/off button on the XM 1800 remote panel does not disconnect DC or AC input power to the XM 1800.

There are two tests to be performed. The first test verifies that the XM 1800 is inverting DC power from the batteries to provide AC power to operate AC devices.

The second test is intended for installations where AC input and output is hardwired to the XM 1800. The test verifies that the XM 1800 transfers from inverter power to shore power when shore power is present.

Note: Shore power (pass-through) refers to the AC input power from a utility grid, generator or external AC source.

When you are ready to test your installation and operate the XM 1800, close the DC fuse and Disconnect or the DC circuit breaker to supply DC power to the XM 1800.

Testing in Invert Mode

To test the XM 1800 in invert mode:

1.For hardwired installations, ensure shore power is not present.

2.Press the on/off button to turn the inverter on.

The status LED on the display panel glows yellow and the LED display illuminates.

3.Plug an appliance within the power rating of the inverter into the XM 1800 GFCI or an AC outlet hardwired to the XM 1800.

3–24

975-0263-01-01

Page 43
Image 43
Xantrex Technology XM 1000 manual Testing Your Installation, Testing in Invert Mode, To test the XM 1800 in invert mode