BTU Per Hour Input*

Installation

FURNACE LOCATED IN CONFINED SPACE

When the furnace is in utility room, install two open grilles. (See Fig. 28.) Place them in a wall or door opening to the rest of the house. One grille will supply combustion air.

Locate it near the floor. The other grille is for ventilation. Locate it close to the ceiling. Each grille must have a free area. It should be not less than one square inch for each 1000 BTU/hr. of the total input rating of appliances in confined space.

FOR EXAMPLE: Your furnace is rated at 150,000 BTU per hour. The water heater is rated 30,000 BTU per hour. The total is 180,000 BTU per hour. You need two grilles, each with 180 square inches of free opening. Metal grilles have about 60% free (open) area. Therefore, you need two metal grilles with 300 square inches each of louvered area. The height should be about half the width.

FRESH AIR DUCT CAPACITIES

FIG. 28

Fresh air duct capacities for duct supplying fresh air

 

BTU Per Hour Input*

 

1/4” MESH

WOOD

METAL

 

SCREEN

LOUVERS

LOUVERS

SIZE

BTU

BTU

BTU

 

 

 

 

3-1/4 X 12 INCH

144,000

36,000

108,000

8 INCH ROUND

200,000

50,000

150,000

8 X 12 INCH

382,000

96,000

288,000

8 X 16 INCH

512,000

128,000

384,000

 

 

 

 

* Based on opening covered by 1/4 inch mesh screen, wood or metal louvers.