Troubleshooting

Troubleshooting

SERVICE HINTS- OIL

Problem: If your furnace is not heating or giving enough heat.

 

Cause: Thermostat is not set correctly

 

 

Correction: Check to see that thermostat is set on "HEAT" position and heat

 

 

 

anticipator is set properly. Reset thermostat above room temperature.

 

 

 

 

 

 

 

 

 

 

 

Cause: Burner is not firing properly

 

 

Correction: Contact your local service man

 

 

 

 

 

 

 

 

 

Cause: No power to furnace

 

Correction: Check fuse or circuit breaker. If fuse is blown, replace. IF

 

 

 

 

breaker is tripped, reset. Check to be sure shut-off switch is “ON”.

 

 

Cause: No oil in tank

 

Correction: Check oil tank gauge. If empty, have tank filled and start burner.

 

 

 

 

 

 

Cause: Valve in oil line is closed

 

 

Correction: Open valve in oil line and start burner

 

 

 

 

 

 

 

 

 

 

 

Cause: Oil filter is plugged

 

 

Correction: Replace filter cartridge

 

 

 

 

 

 

Cause: Cycling on limit control

 

 

Correction: Check to see limit control pointer is set against stop at 250º F.

 

 

 

 

Clean or replace air filter if dirty. Check to be sure all registers and grilles are

 

 

 

 

 

 

 

 

open and not disturbed.

 

 

 

 

 

 

 

SERVICE HINTS-GAS

 

 

 

 

 

 

 

 

 

 

What’s Wrong?

 

WHY?

 

 

 

 

 

 

 

Lockout occurs 3-10 seconds after ignition

 

Reverse polarity.

 

 

 

 

• System improperly grounded

 

 

 

 

• Gas pressure too high, causing flame to lift off burner.

 

 

 

 

• Sensor probe incorrectly positioned in flame pattern.

 

 

 

 

 

Flame not established

 

Spark gap too small

 

 

 

 

 

 

 

 

 

 

 

Arcing to ground

 

Spark too large

 

 

 

 

 

Weak spark

 

Broken high voltage lead.

 

 

 

 

• High voltage lead too close to metal surface.

 

No flame

 

Valve malfunction.

 

Low flame current and/or nuisance

 

Electrode improperly placed.

 

lockouts

 

 

 

 

Nuisance lockouts

 

Flame current falls below 2.5 A.

 

 

• Low gas pressure.

 

 

 

 

 

Problem: If you do not seem to be getting enough air circulation....

 

 

 

 

 

 

 

Cause: Air filter is dirty

 

Correction: Clean or replace air filter as necessary

 

 

 

 

 

Cause: Registers and grilles are

 

Correction: Check supply or damper positions. Check registers and

 

obstructed

 

grilles to make sure they are not closed. Also, make sure they are not

 

 

 

 

obstructed by carpet, draperies or furniture. Remove any obstructions.

 

 

 

 

 

 

 

 

 

 

 

 