Unigreen Minibar, Ventagli, Super Spalliera, RV-GDC Batching Taps see Picture, Calibrated Plates CP

Page 21

For instance, having a mistblower with fans and knowing:

-the working length L = 4,0 meters;

-the forward speed of 5,0 km/h;

-the tap lever in position 2;

-the pressure adjusted at 2,0 bars

you will have a flow rate value of 7,0 l/min. and consequently of 210 l/ha.

Similarly, by knowing the l/ha value to be sprayed, as well as the working speed and distance, we can obtain the lever position and the pressure which is necessary for treatment.

As the speed values indicated in the tables will hardly correspond to the real ones, at first it will be necessary to calibrate the speed by operating in the following way. With the equipment in average working conditions (half-filled tank), with power take-off at 500 r.p.m. and with the fan/s in operation (without spraying), drive a measured base of 100 meters, possibly on the field on which you have to work and measure the time (t) in seconds that you need to drive it.

Then calculate speed according to the formula:

V = S x 3,6 (1)

t

whereas S is the distance in meters (in our case, 100 meters) and t is the

time necessary to drive it.

 

Example:

 

if t = 66 seconds, you will have

V = 100 x 3,6 = 5,4 km/h

 

66

It is recommended to repeat the calibration with 2-3 different gears in order to have more data relating to speed.

As - beyond forward speed - also working width may not correspond to the ones indicated on the table, by using the flow rate in l/min. of the spraying head (see last line of table No. 3), you may obtain the volume in l/ha according to the following formula (2):

VOLUME in l/Ha. =

600 x l/min.

(2)

 

working width (m) x working speed (km/h)

 

Therefore, if from the initial example only working speed is different from V =

5,4 km/h, you will have:

volume in l/ha = 600 x 7

= 194 l/ha

 

4 x 5,4

 

If also working width is different, for instance 3,5 m:

volume in l/ha =

600 x 7

= 222 l/ha

 

3,5 x 5,4

 

6.4.1BATCHING TAPS (SEE PICTURE 20)

On the equipment VENTAGLI (FANS) there are two batching taps which can be used to quickly change the flow rate to the jets; the long part of the lever shows the position (f.i. picture 20 = pos. 4). Each tap can carry out four different positions. In the range of each single mode, for four different pressures set on the regulator, we obtain four different values of the litre capacity per minute, for a total of 16 values as you can observe from table pages 25-26. An increase in pressure means an increase in capacity; a decrease in pressure means a decrease in capacity. For other types of heads, the number of positions and the pressure value can be different, as you can notice on the relevant tables.

6.4.2 CALIBRATED PLATES CP

In the accessories provided with an anti-dripping valve on each sprayer, on the valve output there is a calibration plate which guarantees an homogeneous distribution among the various sprayers.

According to the spraying table to be carried out, it is necessary to install the plate indicated in the table.

NOTE: The plate must be mounted with the side bearing the initials towards the liquid output (picture 21).

The values indicated on the tables are approximate; according to the mixture concentration, spraying values can be slightly different. These differences can be easily corrected by acting on the working pressure. Increasing pressure means increasing spraying and vice versa.

N.B. to calculate the different ranges it is sufficient to multiply the value lt/hectare by the corresponding width indicated in the table and divide it by the new width.

Example-

In the table: 907lt/ha with row distance 3m.

907x3 = 971 Lt/ha with row distance 2,8m

2,8

FIG. 20

posiz.

Ømm

Ø inch

 

 

 

1

Ø1,75

Ø0,07"

2

Ø2,25

Ø0,09"

3

Ø3,50

Ø0,14"

4

Ø4,25

Ø0,17"

FIG. 21

ANTIDRIPPING VALVE

MARKED SIDE

GASKET

CALIBRATED PLATE

 

 

4916-47

 

 

4916-51

 

 

4916-55

unigreen 21

 

4916-70

Image 21
Contents 09/2006 USE and Maintenance ManualSummary Hand Lances Maintenance Guarantee Using and Keeping the USE and Maintenance ManualComposition of the Manual Product Responsibility Unigreen spa is not responsible ifKey to the symbols Intended USE Using Chemical ProductsProhibited USE Regulations for the USE of Chemical ProductsWeather Conditions Characteristics and SpecificationsDriving on the Road Tables of Fittings AllowedStandards of Reference Noise Level of the MachineInstructions Description of the MachinePreliminary Checks Transporting and Moving the MachineTowed Atomisers Parking THREE-POINT Coupling Tractor CouplingFor verification use the formula shown here Hydraulic Connection to the DistributorsCardan Shaft PumpSuction Filter Components of the Pressure Regulator Pressure RegulatorControl box for GCP Elettrico electrical regulators General InstructionsDelivery Filters only Equipped Models Auxiliaries Taps BlockTank rinsing Ejector Agitator Filling the Tank Test with Clean WaterManual Premixing Mixing12.2PREMIXER on Cover Optional 12.4COVER Washer for Chemical Containers13.1CIRCUIT Washer and Tank Washer Washing the AtomiserBlower Group Multiplier FAN UnitClutch Ventagli Fans CANOPY, and Espalier Distributors Minibar for EspalierSuper Spalliera for Espalier Hydraulics RV Boom for GDCOIL Feed from Tractor for hydraulic systems RV per GDCNON-DRIP Valve Spraying Description of the DiffusersDescription of the MFC Nozzles Mistblower CalibrationCalibrated Plates CP Batching Taps see PictureProgrammed Maintenance MaintenanceRoutine Maintenance Cleaning the NozzlesPutting Back Into Service After Winter Layup Extraordinary MaintenanceMultiplier Lubrication RepairsDemolition and Disposal Materials for DemolitionElectrical and Electronic Apparatus Waste Eeaw Tables for Calibrating Airdrop 2 Ventagli Fans Airdrop Calibrating TablesTables for Calibrating Airdrop 2 Ventagli + TOP Diffusors OptionalTables for Calibrating Airdrop Minibar Piastrina CalibrataTables for Calibrating Airdrop RV-GDC Tables for Calibrating Airdrop Super SpallieraTables of Delivery of Nozzles for Hand Lances 50 h 300 h Table of Programmed Maintenance OperationTAB a TAB.18A Allowed FittingsMember of the group