SECTION 6: HEATER INSTALLATION
FIGURE 14: Critical Hanger Placement
Typical Suspension Details
| Beam Clamp |
|
|
| Anchor |
|
| Screw Hook |
|
| 3/8" |
|
| Chain Size |
| Rod 3/8" | 3/16" |
24" min.* | Minimum | |
|
| |
(61 cm) | “X”* |
|
|
| |
|
|
Concrete Beam Locknut Wood Beam
Washers
Turnbuckle | * Allows for thermal expansion of system |
Not Included |
|
| |
Side View |
| Hanger |
Hanger |
|
|
Reflector |
|
|
Must Be Within 4" (10 cm) | Front View | 45° Angle |
Description | Part Number |
91907302 | |
|
|
Tube/Reflector Hanger | 03090100 |
|
|
Run Length | Typical Expansion | Minimum “X” Length |
10' (3 m) - 50' (15.2 m) | ±1" (3 cm) | 12" (30.5 cm) |
|
|
|
51' (15.5 m) - 60' (18.3 m) | ±2" (5 cm) | 18" (45.7 cm) |
|
|
|
61' (18.6 m) - 80' (24.4 m) | ±3" (8 cm) | 24" (61 cm) |
|
|
|
15 of 59