Menu 10 : General settings

General settings for identifying the unit.

10.1Temperature units >C

 

 

The units that temperatures will be displayed. Either degrees C, or degrees F.

10.2

Sample rate

>10 minutes

 

 

The interval time in Minutes (1, 2, 3,..,15, 20, 25, 30,.., 60 minutes) for storing

 

 

a temperature measurement into memory.

10.3

Vehicle ID

>AB-1234

 

 

16 characters are available for assigning a vehicle identification. It is

 

 

necessary to enter an identification like registration number or chassis number

 

 

in the case of a trailer. The vehicle ID will be shown on every printout in the

 

 

header together with the serial number and Header text.

10.4

Header text

>Abcdef

 

 

16 characters are available for assigning a header tittle (usually the company

 

 

name). The header text will be shown on every print out together with the

 

 

Vehicle ID and serial number.

10.5

PIN code

>1111

 

 

The PIN code is intended to avoid having unauthorised people access to

 

 

changing parameters which can influence a correct recorder operation. Select

 

 

a code between 1111 and 9999. The factory setting is 1111. (digit “0“ is not

 

 

available.)

 

 

Attention : Do not forget to note the new PIN code and store it in a safe

 

 

place. There is no master code available to get later access to the parameter

 

 

menu.

10.6

Correction factor

>+0

 

 

Correction factors from –9 to +9 for calibrating the temperature sensing

 

 

circuitry. To be used with diagnostic procedure “set correction factor”. See

 

 

enclosure D and field diagnostic instructions.

10.7

Serial number

>11200231

 

 

Displays only the serial number of the recorder. The number will be set at

 

 

factory and cannot be changed. The serial number will be on every print out.

Menu 11 : Communication settings

Following settings enable you to configure communication with internal options or external devices.

11.1 COM1 RS-232 port setting

The COM1 RS-232 port can be configured with :

No protocol

Third party: light protocol to extract part of the data from the recorder.

TMS protocol (9,600 Baud): current protocol to extract all data from the recorder.

DECT protocol: to communicate with optional in-built DECT module.

GSM protocol: to communicate with optional in-built GSM module.

TMS protocol (38,400 Baud):

Page 21

62-61138-20 (02/03)

Image 21
Contents Installation USER’S Manual DataCOLD 500 T DataCOLD 500 RTable of Contents Blue General descriptionYellow Green EditInstallation PrinterPositioning Connections Mounting DataCOLD R-VersionOptional junction box CON4 Optional Mounting kitConnectors Power supplyDataCOLD T-Version Is not Used for More than TEN 10 Days Wiring Alarm outputsConfiguration Display background lighting preferable for the R-VersionTemperature sensors Final testing Standard InstallationSupplementary installation Alarm signalUser menus Page Alarm menu Day start timeDay end time Time setting User settingsSummer / wint time setting Date settingKeyboard back light setting Display back light settingBuzzer volume setting Buzzer frequency settingParameter menu Menu 5 Temperature inputs settingsT1 Input On/off Return airT3 Input On/off. Menu structure as T4 Input Digital inputs setting On/off Menu 6 Digital inputs settingsMenu 7 Compartment settings Compartment On/offAlarm group On/off Menu Alarm settingsMenu 9 Printer settings Delivery ticket settingsTemperature units C Menu 10 General settingsMenu 11 Communication settings 10.2 Sample rate Minutes11.2 COM2 RS-232 port setting Part Number Designation Accessories and spare parts62-61138-20 02/03 Enclosure a Enclosure B Replace paper roll Temperature inputs Factory setting Enclosure C Factory settingsCompartment settings Printer settingsEnter Pincode Enclosure D Failure codes & Set correction factor procedureDigital Inputs configuration example Enclosure E Wiring diagrams= GND = RXD = TXD = CTS