Raypak RP2100 operating instructions Electrical Wiring, Millivolt System, Electronic

Page 24

ELECTRICAL WIRING

NOTE: If it is necessary to replace any of the original wiring, it must be replaced with 105° C wire or its equivalent, and/or 150° C wire or its equivalent as originally built.

MILLIVOLT SYSTEM

The Millivolt System residential heater is equipped with a self-generating electrical system in which the electric current is provided by means of a pilot generator. No external electrical connections are required.

When installing a remote switch, do not exceed 10 feet of wiring from the heater. Use 18 gage stranded wire.

ELECTRONIC

INTERMITTENT IGNITION DEVICE SYSTEM (IID)

NOTE:

Heaters are factory wired for 240V power supply.

The standard field wiring connection is on the right side of the heater.

To wire the heater from the left side, follow the steps below:

1.Remove the two (2) screws that hold down the junction box to the sway brace. Untie excess yellow wires located behind the junction box.

2.Move the junction box to the left side of unit and attach the box to the sway brace.

3.Secure 24V yellow wires to sway brace panel with existing wire retainers.

4.Connect the wires inside the junction box, either 120V or 240V depending on the field wiring.

NOTE: 7/8" Dia. holes not utilized on jacket and control box can be used for fireman switch or auxiliary control interface wiring.

NOTE: Heater must be electrically grounded and bonded. Bonding lug is provided loose with the unit. Install bonding lug on lower right or left side of jacket as necessary for bonding the unit. Mounting hole is provided on the jacket.

The Electronic Intermittent Ignition Device automatically lights the pilot and main burners upon a call for the heat. The heater is supplied with a dual voltage transformer for 120V or 240V input power hookup.

Option Location For Left

Control Box

Side Field Wiring

(Factory Mounted Location)

Sway

Brace

Bonding Lug

Fig. # 9470

Bonding Lug

(Optional Location)

 

(Standard Location)

ATMOSPHERIC

Wiring locations

Fig.# 9366.1

LOW NOx

Wiring locations

24

Image 24
Contents Installation and Operating Instructions What to do if YOU Smell GASPage Contents START-UP Procedures For Your Safety Read Before OperatingBefore START-UP Burners Water Millivolt System Lighting InstructionsTo Turn OFF GAS to Appliance Electronic Ignitions Systems What to do if YOU Smell GASOperating Instructions Maintenance and Care Procedures Water Pressure SwitchAfter START-UP Visual InspectionPool & SPA Water Chemistry Automatic Chlorinators Chemical FeedersCold Weather Operation Winterizing the Pool & SPA Heater General Specifications Receiving EquipmentStandardunitpolymerheaders Asme Unit Cast Iron Headers Installation Instructions Outdoorheaterinstallation Installations onlyIndoor Heater Installation Outdoor KIT IncludesIndoor KIT Includes Installing the Clips Indoor & Outdoor Kits Securing the TOP Panel Cover Indoor KIT onlySecuring the TOP Panel Cover Outdoor KIT only Installing the TOP Cover Outdoor KIT only Specifications and Dimensions Combustion and Ventilation AIR Indoor Units OnlyVent Piping GAS Supply ConnectionsGAS Pressure Adjustment Locations GAS Pressure RegulatorPipe Sizing for GAS Connections Plumbing for Water Connections Flow RatesCast Iron Headrers Asme Models Unitherm Governor OperationExternal Auxiliary Bypass Valve Where Required Auxiliary Bypass Valve AdjustmentHeat Exchanger Pressure Drop Tables Heat Exchanger Reversal Procedure Polymer Header Models For Asme Models call your factory representativeElectrical Wiring Millivolt SystemElectronic Transformer Wiring 120V Wiring 240V WiringIndependently Wiring Diagram Millivolt Mechanical Thermostat Wiring Diagram IID Atmospheric Wiring Diagram IID Low NOx General Location of Controlscontrol Adjustments Control Panel RemovalMillivolt Controls Digital Thermostat Controls Thermostat Control OperationFahrenheit vs Centigrade Diagnostics Reading a FaultDisplay Definition Remote Control Installation and Operation Remote OperationActivating the Remote Remote Control Wiring Wire Remote Control On-OffPressure Switch Flame ROLL-OUT Safety SwitchPilot SAFETY- Millivolt Pilot SAFETY- ElectronicPilot Removal and Cleaning Burner Drawer RemovalGAS Valve Removal Main Burner and Orifice RemovalTubecleaningprocedure DesootingprocedureImmersion Well Replacement Unitherm Governor U.G. ReplacementSTART-UP Procedures BurneradjustmentBlower Adjustment Flame ROLL-OUT Safety SwitchPilot Removal Combustion FAN RemovalTroubleshooting Guide MechanicalforqualifiedservicepersonnelonlyElectrical Standing Pilot Millivolt Raypak Pool or SPA Heater Electrical Check with MV GAS ValveElectrical Electronic Ignition IID Troubleshooting For qualified technicians onlyDigital Control Logic Flow Chart Replacement Parts RAYPAK, INCEastman Avenue Oxnard, CA For Canada Illustrated Parts List Pilot Assemblies Page Page Page Page Page
Related manuals
Manual 46 pages 34.19 Kb

P-R185B to R-P405B, C-R185B to C-R405B, P-R185BL to P-R405BL, C-R185BL to C-R405BL, RP2100 specifications

Raypak is a leading manufacturer in the heating and cooling industry, renowned for its innovative products that cater to both residential and commercial sectors. One of its product lines, the RP2100 series, exemplifies cutting-edge technology and features designed to enhance efficiency and performance in pool heating systems.

The RP2100 models, particularly the P-R185B through R-P405B series, incorporate advanced heat exchanger technology, enabling them to offer exceptional heat transfer efficiency. The titanium heat exchangers are designed for durability and resistance against corrosion, particularly in saltwater environments, ensuring the longevity of the system. These units are engineered for both outdoor and indoor applications, with the versatility to adapt to various heating requirements.

In terms of energy efficiency, the RP2100 series boasts a high coefficient of performance (COP), making them cost-effective solutions for pool heating. They are equipped with digital thermostats that provide accurate temperature control, ensuring consistent heating capabilities while minimizing energy consumption. The inclusion of intelligent controls allows for seamless integration with existing systems and provides users with the ability to schedule heating cycles, further enhancing energy savings.

Moving beyond the RP2100 series, the C-R185B to C-R405B models are specifically tailored for commercial applications, combining robust performance with user-friendly features. These commercial heaters are designed to handle larger volumes of water and are built to withstand the rigors of high-traffic environments, such as resorts and sports complexes. Their vertical design optimizes space and promotes better airflow, which is crucial in high-demand scenarios.

The P-R185BL to P-R405BL and C-R185BL to C-R405BL models feature noise-reducing technology, making them suitable for residential settings where peace and quiet are paramount. They utilize advanced acoustic insulation materials that minimize operational noise without sacrificing performance.

In summary, the Raypak RP2100, P-R185B to R-P405B, C-R185B to C-R405B, P-R185BL to P-R405BL, and C-R185BL to C-R405BL series represent the pinnacle of innovation in pool heating solutions. With their durable construction, energy-efficient designs, and advanced technologies, these models are ideal for users seeking reliability, efficiency, and quiet operation in both residential and commercial environments. Investing in Raypak products ensures superior heating performance, longevity, and overall satisfaction.