SECTION 5 - TROUBLESHOOTING GUIDE

MECHANICAL(FORQUALIFIEDSERVICEPERSONNELONLY)

IMPORTANT NOTICE These instructions are primarily intended for the use of qualified personnel specifically trained and experienced in the installation of this type of heating equipment and related system components. Installation and service personnel may be required by some states to be licensed. Persons not qualified shall not attempt to install this equipment nor attempt repairs according to these instructions.

PROBLEM

CAUSE

 

SOLUTION

 

 

 

 

 

 

Harmonics, or whining noise

U.G. inoperative

Check movement by putting in hot water (110°F or

 

 

 

 

higher). If no movement, replace.

 

*Debris or restriction in system

Locate the restriction and remove. Flush system

 

 

 

 

and clean.

 

 

 

*Debris in gas line

Remove debris or blow out gas line.

 

Low

flow

Scale forming in heat exchanger - clean heat

 

 

 

 

exchanger and check pool pH and total alkalinity.

 

 

 

 

 

 

 

Heater going on and off

Dirty

filter

Backwash filter.

 

 

continuously

Low water level in pool

Raise water level.

 

External bypass setting out of

 

 

 

 

 

adjustment

Adjust

bypass

 

 

 

*Pressure switch out of

 

 

 

 

 

adjustment

Adjust

pressure

switch

 

 

 

 

Liming or scale forming on

Pool water

Recommended pH should be between 7.4 and 7.8

heat exchanger

 

 

 

Total alkalinity 100-150 PPM maximum.

 

 

 

 

Hardness 150-400 PPM maximum.

Sooting

High

flow

rates

Reduce by adding manual bypass valve. Adjust

 

 

 

 

manual bypass valve until heater outlet water

 

 

 

 

temperature is between 105° and 110°F.

 

U.G. Inoperative

Check movement by putting in hot water (110°F

 

 

 

 

or higher). If no movement, replace.

 

*Air

starvation

Refer to installation instructions.

 

*Improper venting

Follow recommended installation instructions.

 

*Insects or debris clogging

 

 

 

 

 

burner intake ports

Clean burners.

 

 

 

 

 

 

 

 

Pilot outage

Low

gas

pressure

Adjust gas pressure.

 

Restricted

pilot

Clean pilot.

 

 

 

Weak pilot generator

Replace pilot.

 

 

 

 

 

 

 

 

Yellow lazy flame

Low

gas

pressure

Adjust gas pressure.

 

*Insects or debris clogging

 

 

 

 

 

burner intake ports

Clean burners.

 

 

 

 

 

 

 

 

Outer jacket very hot

*Broken refractory caused by

 

 

 

 

(paint blistered)

shipping damage or improper

 

 

 

 

 

combustion

Replace refractory panels.

 

Excessive sooting of heat

 

 

 

 

 

exchanger

Determine cause of sooting & correct.

 

 

 

 

 

Takes long time to heat

Calculate temperature in °/hr

Heat rise (°/hr.)=

Htr. output

pool or spa.

 

 

 

 

 

Pool gallonage x 8.33

 

 

 

 

 

or refer to heater sizing chart. This does not take into

 

 

 

 

account heat loss due to weather.

 

Filter not running long enough

Reset time clock.

 

 

 

Dirty

filter

Clean filter.

 

 

 

Gas line or meter undersized

Refer to installation instructions.

 

 

 

 

Liming

Bypassing too much water

Inspect bypass for movement, if no movement,

 

 

 

 

replace.

 

 

 

U.G. not functioning

Replace if no movement when heated.

 

 

 

 

 

Leaking at well.

Overacid

Replace well and maintain water chemistry properly.

 

 

 

 

 

Leaking at heat exchanger.

Overacid

Replace heat exchanger and maintain chemistry

 

 

 

 

properly.

 

 

 

 

 

 

 

 

Gasket brittle and leaking -

Heater running after pump

 

 

 

 

(overheated).

shuts off

See pressure switch adjustment.

 

Refractory damage

Replace refractory.

 

Sooted heater

Determine cause of sooting and correct.

Combustion fan not running

Fan

relay

Replace fan relay

 

Fan

 

Loose connection or failed motor

 

Burned motor

Incorrect wiring,

replace blower

* Indicates symptom which usually occurs on initial start-up.

39

Image 39
Contents What to do if YOU Smell GAS Installation and Operating InstructionsPage Contents START-UP Procedures For Your Safety Read Before OperatingBefore START-UP Burners Water Millivolt System Lighting InstructionsTo Turn OFF GAS to Appliance Electronic Ignitions Systems What to do if YOU Smell GASOperating Instructions Visual Inspection Maintenance and Care ProceduresWater Pressure Switch After START-UPPool & SPA Water Chemistry Automatic Chlorinators Chemical FeedersCold Weather Operation Winterizing the Pool & SPA Heater General Specifications Receiving EquipmentStandardunitpolymerheaders Asme Unit Cast Iron Headers Installation Instructions Installations only OutdoorheaterinstallationIndoor Heater Installation Outdoor KIT IncludesIndoor KIT Includes Installing the Clips Indoor & Outdoor Kits Securing the TOP Panel Cover Indoor KIT onlySecuring the TOP Panel Cover Outdoor KIT only Installing the TOP Cover Outdoor KIT only Combustion and Ventilation AIR Indoor Units Only Specifications and DimensionsGAS Supply Connections Vent PipingGAS Pressure Adjustment Locations GAS Pressure RegulatorPipe Sizing for GAS Connections Flow Rates Plumbing for Water ConnectionsUnitherm Governor Operation Cast Iron Headrers Asme ModelsAuxiliary Bypass Valve Adjustment External Auxiliary Bypass Valve Where RequiredHeat Exchanger Pressure Drop Tables For Asme Models call your factory representative Heat Exchanger Reversal Procedure Polymer Header ModelsElectrical Wiring Millivolt SystemElectronic Transformer Wiring 120V Wiring 240V WiringIndependently Wiring Diagram Millivolt Mechanical Thermostat Wiring Diagram IID Atmospheric Wiring Diagram IID Low NOx General Location of Controlscontrol Adjustments Control Panel RemovalMillivolt Controls Digital Thermostat Controls Thermostat Control OperationFahrenheit vs Centigrade Diagnostics Reading a FaultDisplay Definition Remote Control Installation and Operation Remote OperationActivating the Remote Wire Remote Control On-Off Remote Control WiringPilot SAFETY- Electronic Pressure SwitchFlame ROLL-OUT Safety Switch Pilot SAFETY- MillivoltMain Burner and Orifice Removal Pilot Removal and CleaningBurner Drawer Removal GAS Valve RemovalUnitherm Governor U.G. Replacement TubecleaningprocedureDesootingprocedure Immersion Well ReplacementFlame ROLL-OUT Safety Switch START-UP ProceduresBurneradjustment Blower AdjustmentCombustion FAN Removal Pilot RemovalMechanicalforqualifiedservicepersonnelonly Troubleshooting GuideRaypak Pool or SPA Heater Electrical Check with MV GAS Valve Electrical Standing Pilot MillivoltFor qualified technicians only Electrical Electronic Ignition IID TroubleshootingDigital Control Logic Flow Chart Replacement Parts RAYPAK, INCEastman Avenue Oxnard, CA For Canada Illustrated Parts List Pilot Assemblies Page Page Page Page Page
Related manuals
Manual 46 pages 34.19 Kb

P-R185B to R-P405B, C-R185B to C-R405B, P-R185BL to P-R405BL, C-R185BL to C-R405BL, RP2100 specifications

Raypak is a leading manufacturer in the heating and cooling industry, renowned for its innovative products that cater to both residential and commercial sectors. One of its product lines, the RP2100 series, exemplifies cutting-edge technology and features designed to enhance efficiency and performance in pool heating systems.

The RP2100 models, particularly the P-R185B through R-P405B series, incorporate advanced heat exchanger technology, enabling them to offer exceptional heat transfer efficiency. The titanium heat exchangers are designed for durability and resistance against corrosion, particularly in saltwater environments, ensuring the longevity of the system. These units are engineered for both outdoor and indoor applications, with the versatility to adapt to various heating requirements.

In terms of energy efficiency, the RP2100 series boasts a high coefficient of performance (COP), making them cost-effective solutions for pool heating. They are equipped with digital thermostats that provide accurate temperature control, ensuring consistent heating capabilities while minimizing energy consumption. The inclusion of intelligent controls allows for seamless integration with existing systems and provides users with the ability to schedule heating cycles, further enhancing energy savings.

Moving beyond the RP2100 series, the C-R185B to C-R405B models are specifically tailored for commercial applications, combining robust performance with user-friendly features. These commercial heaters are designed to handle larger volumes of water and are built to withstand the rigors of high-traffic environments, such as resorts and sports complexes. Their vertical design optimizes space and promotes better airflow, which is crucial in high-demand scenarios.

The P-R185BL to P-R405BL and C-R185BL to C-R405BL models feature noise-reducing technology, making them suitable for residential settings where peace and quiet are paramount. They utilize advanced acoustic insulation materials that minimize operational noise without sacrificing performance.

In summary, the Raypak RP2100, P-R185B to R-P405B, C-R185B to C-R405B, P-R185BL to P-R405BL, and C-R185BL to C-R405BL series represent the pinnacle of innovation in pool heating solutions. With their durable construction, energy-efficient designs, and advanced technologies, these models are ideal for users seeking reliability, efficiency, and quiet operation in both residential and commercial environments. Investing in Raypak products ensures superior heating performance, longevity, and overall satisfaction.