DV425TR DIRECT VENT ROOM HEATER
TROUBLE SHOOTING (continued)
| PROBLEM |
| POSSIBLE CAUSE: |
| SOLUTIONS: |
|
|
|
|
| |||
| Pilot will not Hold |
| Defective Magnet |
| If the mV reading is above 6mV and the Safety Magnet does |
|
| (Cont.) |
| (mV Plus systems). |
| not hold, replace the Valve. |
|
|
|
|
|
| (E) If |
|
|
|
|
|
| Circuit reading, the Coil is electrically "Open". Replace the |
|
|
|
|
|
| Valve. |
|
|
|
|
|
|
|
|
|
|
| Defective Safety Magnet |
| Verify operation of Safety Magnet in the following manner: |
|
|
|
| (milliVolt System) |
| (A) Remove all Wires from the Terminals of the Main |
|
|
|
|
|
| Operator. |
|
|
|
|
|
| (B) Measure the electrical voltage between the Termihals |
|
|
|
|
|
| TPTH and TP. If the voltage is above 110mV and the Safety |
|
|
|
|
|
| Magnet does not hold, replace the Valve. |
|
|
|
|
|
|
|
|
| Pilot Drops Out. |
| Pilot Orifice blocked. |
| Replace Orifice with a new Orifice of the exact size and type. |
|
|
|
|
|
|
|
|
|
|
| Wrong Pilot Orifice. |
| Replace the Orifice with a new Orifice supplied specifically |
|
|
|
|
|
| for the appliance and gas in question. |
|
|
|
|
|
|
|
|
| No gas to Main |
| Low gas pressure to |
| Check Gas Pressure (&" NG/11"LP) |
|
| Burner |
| appliance. |
|
|
|
|
|
| Pilot not lit. |
| Light Pilot and wait for |
|
|
|
|
|
| sufficiently to power the Main Operator. If Pilot fails to light, |
|
|
|
|
|
| hold, hold, refer to the above sections. |
|
|
|
|
|
|
|
|
|
|
| Control Knob in the "ON" |
| Rotate "OFF/PILOT/ON" Control Knob to the "ON" position. |
|
|
|
| position. |
|
|
|
|
|
|
|
|
|
|
| Thermostat/Wall |
| Thermostat not in the "ON" |
| Turn Thermostat "ON" and then adjust Temperature Control |
|
| Switch will not |
| position. |
| to call for heat. |
|
| cycle the Main |
|
|
|
|
|
|
|
|
|
|
| |
| Burner. |
|
| If unable to meet minimum requirements, replace the |
| |
|
|
| voltage not within design |
|
| |
|
|
| parameters. |
|
|
|
|
|
| Defective Thermostat or |
| (A) With the apilot adjusted properly, place a Jumper Wire |
|
|
|
| Thermostat Wiring. |
| between TPTH and TH. Take a mV reading across the TPTH |
|
|
|
|
|
| and TH Terminals of the Valve. This Closed Circuit voltage |
|
|
|
|
|
| should not fall below 300mV. Record reading. |
|
|
|
|
|
| (B) Remove Jumper wire from the TPTH and TH conections |
|
|
|
|
|
| and connect the Thermostat Wires to the same Terminals. |
|
|
|
|
|
| Closed Circuit voltage as described in the previous Step. If |
|
|
|
|
|
| the mFV reading drops below 150mV, excessive resistance |
|
|
|
|
|
| exists in the Thermostat Circuit and must be isolated and |
|
|
|
|
|
| eliminated. |
|
|
|
|
|
|
|
|
|
|
| Defective Wall Switch. |
| Repeat the above troubleshooting items covered under |
|
|
|
|
|
| "Defective Thermostat or Thermostat Wiring" except, |
|
|
|
|
|
| substitute the words "Wall Switch" where the word |
|
|
|
|
|
| Thermostat appears in the instructions. |
|
|
|
|
|
|
|
|
02/01 | Page 55 |