Sapphire Audio DV425TR owner manual TROUBLE SHOOTING continued

Models: DV425TR

1 60
Download 60 pages 11.22 Kb
Page 55
Image 55
TROUBLE SHOOTING (continued)

DV425TR DIRECT VENT ROOM HEATER

TROUBLE SHOOTING (continued)

 

PROBLEM

 

POSSIBLE CAUSE:

 

SOLUTIONS:

 

 

 

 

 

 

Pilot will not Hold

 

Defective Magnet

 

If the mV reading is above 6mV and the Safety Magnet does

 

 

(Cont.)

 

(mV Plus systems).

 

not hold, replace the Valve.

 

 

 

 

 

 

(E) If closed-Circuit mV reading is the same as the Open-

 

 

 

 

 

 

Circuit reading, the Coil is electrically "Open". Replace the

 

 

 

 

 

 

Valve.

 

 

 

 

 

 

 

 

 

 

 

Defective Safety Magnet

 

Verify operation of Safety Magnet in the following manner:

 

 

 

 

(milliVolt System)

 

(A) Remove all Wires from the Terminals of the Main

 

 

 

 

 

 

Operator.

 

 

 

 

 

 

(B) Measure the electrical voltage between the Termihals

 

 

 

 

 

 

TPTH and TP. If the voltage is above 110mV and the Safety

 

 

 

 

 

 

Magnet does not hold, replace the Valve.

 

 

 

 

 

 

 

 

 

Pilot Drops Out.

 

Pilot Orifice blocked.

 

Replace Orifice with a new Orifice of the exact size and type.

 

 

 

 

 

 

 

 

 

 

 

Wrong Pilot Orifice.

 

Replace the Orifice with a new Orifice supplied specifically

 

 

 

 

 

 

for the appliance and gas in question.

 

 

 

 

 

 

 

 

 

No gas to Main

 

Low gas pressure to

 

Check Gas Pressure (&" NG/11"LP)

 

 

Burner

 

appliance.

 

 

 

 

 

 

Pilot not lit.

 

Light Pilot and wait for Thermo-generator to heat up

 

 

 

 

 

 

sufficiently to power the Main Operator. If Pilot fails to light,

 

 

 

 

 

 

hold, hold, refer to the above sections.

 

 

 

 

 

 

 

 

 

 

 

Control Knob in the "ON"

 

Rotate "OFF/PILOT/ON" Control Knob to the "ON" position.

 

 

 

 

position.

 

 

 

 

 

 

 

 

 

 

 

Thermostat/Wall

 

Thermostat not in the "ON"

 

Turn Thermostat "ON" and then adjust Temperature Control

 

 

Switch will not

 

position.

 

to call for heat.

 

 

cycle the Main

 

 

 

 

 

 

 

 

 

 

 

 

Burner.

 

Thermo-generator out-put

 

If unable to meet minimum requirements, replace the

 

 

 

 

voltage not within design

 

Thermo-generator.

 

 

 

 

parameters.

 

 

 

 

 

 

Defective Thermostat or

 

(A) With the apilot adjusted properly, place a Jumper Wire

 

 

 

 

Thermostat Wiring.

 

between TPTH and TH. Take a mV reading across the TPTH

 

 

 

 

 

 

and TH Terminals of the Valve. This Closed Circuit voltage

 

 

 

 

 

 

should not fall below 300mV. Record reading.

 

 

 

 

 

 

(B) Remove Jumper wire from the TPTH and TH conections

 

 

 

 

 

 

and connect the Thermostat Wires to the same Terminals.

 

 

 

 

 

 

Closed Circuit voltage as described in the previous Step. If

 

 

 

 

 

 

the mFV reading drops below 150mV, excessive resistance

 

 

 

 

 

 

exists in the Thermostat Circuit and must be isolated and

 

 

 

 

 

 

eliminated.

 

 

 

 

 

 

 

 

 

 

 

Defective Wall Switch.

 

Repeat the above troubleshooting items covered under

 

 

 

 

 

 

"Defective Thermostat or Thermostat Wiring" except,

 

 

 

 

 

 

substitute the words "Wall Switch" where the word

 

 

 

 

 

 

Thermostat appears in the instructions.

 

 

 

 

 

 

 

 

02/01

Page 55

250-5533

Page 55
Image 55
Sapphire Audio DV425TR owner manual TROUBLE SHOOTING continued