HORIZONTAL TERMINATION REQUIREMENTS

DV425TR DIRECT VENT ROOM HEATER

HORIZONTAL TERMINATION REQUIREMENTS

A.*12” (30cm) minimum: Clearance above grade, veranda, porch, deck, or balcony.

B.*12” (30cm) minimum: Clearance to window or door that may be opened.

C.12” (30cm) minimum: Clearance to permanently closed window (recommended to prevent condensation on window.

D.18” (46cm) minimum: Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2’ (60cm) from the centerline of the terminal.

E. 12” (30cm) minimum: Clearance to unventilated soffit.

F.6” (15cm): Clearance to outside corner.

G.9” (23cm): Clearance to inside corner.

H.*Not to be installed above a meter/regulator (gas or electrical) assembly within 3’ (90cm) horizontally from the centerline of the meter/regulator.

I.72” (1.8m) minimum: Clearance to service regulator vent outlet.

J.*3' (90cm) US; 6' (180cm) Canada minimum: Clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance.

K.*72” (1.8m) minimum: Clearance to a mechanical air supply air inlet.

L.*†84” (2.1m) minimum: Clearance above paved sidewalk or a paved driveway located on public property.

M.*‡12” (30cm) minimum: Clearance under veranda, porch, deck, or balcony.

N.6” (152 mm) minimum: Clearance to outside corner.

†A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single-family dwellings and serves both dwellings.*

‡Only permitted if veranda, porch, deck, or balcony, is fully open on a minimum of two sides beneath the floor.* *As specified in CGA B149 Installation Codes Note: Local Codes or regulations may require different clearances.

NOTE: Refer to page 35 of this manual for Vertical Termination Installations of this appliance.

D

 

 

 

 

 

 

 

N

E

 

 

 

 

 

 

 

 

 

V

 

 

 

 

B

 

 

 

 

 

L

 

Fixed

H

 

 

 

V

Openable

 

 

 

 

Closed

 

 

 

 

 

B

 

 

 

 

 

 

 

F

 

C

I

M

 

G

 

 

K

 

 

A

V

 

A

 

V

 

 

 

J

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

V = vent terminal

A = air supply inlet

= area where terminal is not permitted

02/01

Page 26

250-5533

Page 26
Image 26
Sapphire Audio DV425TR owner manual Horizontal Termination Requirements, V = vent terminal, A = air supply inlet