Raypak RP2100, P-R405A Troubleshooting Honeywell S8600, Electrical Electronic Ignition IID

Page 36

ELECTRICAL (ELECTRONIC IGNITION IID)

WARNING HIGH VOLTAGE

For qualified Technicians ONLY

NOTE: Some heaters may be equipped with an ignition module that shuts off pilot gas if pilot fails to light. To reset, interrupt power to heater.

START

TURN GAS SUPPLY OFF.

TURN THERMOSTAT

(CONTROLLER) TO CALL

FOR HEAT

POWER TO MODULE

(24 V NOMINAL)

YES

Intermittent Pilot System

TROUBLESHOOTING HONEYWELL S8600

NOTE:Before troubleshooting, familiarize yourself with the startup and checkout procedure.

NO

Check line voltage power, low voltage transformer, limit controller, thermostat

(controller) and wiring.

SPARK ACROSS

IGNITER/SENSOR GAP

YES

NO

Pull ignition lead and check spark at module.

Spark Okay?

YES

Check ignition cable, ground wiring, ceramic insulator and gap, and correct.

Check boot of the ignition cable for signs of melting or buckling. Take protective action to shield cable and boot from excessive temperatures.

TURN GAS SUPPLY ON

PILOT BURNER LIGHTS?

YES

SPARK STOPS WHEN

PILOT IS LIT?

YES

MAIN BURNER LIGHTS?

YES

SYSTEM RUNS UNTIL CALL FOR HEAT ENDS?

YES

 

 

• Check that all manual gas valves are open, supply tubing and pressures are good,

NO

 

 

 

 

and pilot burner orifice is not blocked.

 

 

Check electrical connections between module and pilot operator on gas control.

Check for 24 Vac across PV-MV/PV terminals on module. If voltage is okay, replace gas control; if not, replace module.

 

 

 

NOTE:If S8600H goes into lockout, reset system. Lockout is used on L.P.G. models.

 

 

 

 

 

 

 

 

 

 

NO

 

Check continuity of ignition cable and ground wire.

 

 

 

 

Clean flame rod.

 

 

 

Check electrical connections between flame rod and module.

 

 

 

Check for cracked ceramic flame rod insulator.

 

 

 

Check that pilot flame covers flame rod and is steady and blue.

 

 

 

Adjust pilot flame.

 

 

 

If problem persists, replace module.

 

 

 

 

 

 

 

 

Check for 24 Vac across MV-MV/PV terminals. If no voltage, replace module.

NO

 

 

Check electrical connections between module and gas control. If okay, replace

 

 

 

 

 

 

gas valve or gas control operator, i.e. pilot gas valve, flow switch etc.

NOTE: IF S8600H goes into lockout, reset system.

NO

• Check continuity of ignition cable and ground wire.

 

NOTE: If ground is poor or erratic, shutdowns may occur occasionally even though operation is normal at the time of checkout.

Check that pilot flame covers flame rod and is steady and blue.

If checks are okay, replace module.

CALL FOR HEAT ENDS

SYSTEM SHUTS OFF?

YES

TROUBLESHOOTING

ENDS

NO

 

Check for proper thermostat (controller) operation.

 

 

 

Remove MV lead at module; if valve closes, recheck temperature controller and

 

 

 

 

 

wiring; if not, replace gas valve.

Repeat procedure until troublefree operation is obtained.

36

Image 36
Contents Installation Operating Instructions What to do if YOU Smell GASContents START-UP Procedures Before START-UPBurners WaterMillivolt System Lighting InstructionsTo Turn OFF GAS to Appliance Electronic Ignitions Systems What to do if YOU Smell GASOperating Instructions Maintenance and Care Procedures Water Pressure SwitchAfter START-UP Visual InspectionBasic Tips if Heater will not Fire Pool & SPA Water ChemistryAUTOMATICCHLORINATORSANDCHEMICALFEED- ERS ColdweatheroperationGeneral Specifications Receiving EquipmentWinterizing the Pool & SPA Heater Standard Unit Asme UnitInstallation Instructions Heater with Outdoor Stackless TOP Feet horizontallyIndoor Heater Outdoor KIT IncludesSecuring the top panel cover- Indoor KIT only Installing the top cover- Outdoor KIT only Specifications and Dimensions Combustion AIR Indoor Units OnlyVent Piping GAS Supply ConnectionsGAS Pressure Adjustment Locations GAS Pressure RegulatorPipe Sizing for GAS Connections Plumbing for Water ConnectionsFlow Rates Model Pipe Size MIN.GPM MAX.GPM ConnectionsplasticheaderINLET/OUTLETHEADER Companionflangeconnections CastironheaderAuxiliary Bypass Valve Adjustment Pressure Relief Valve InstallationUnithermgovernoroperation Internal Automatic BY-PASS ValveRP2100+ Heat Exchanger Reversal Procedure Jaco Fitting Electricalwiring Millivolt SystemELECTRONICINTERMITTENTIGNITIONDEVICESYS- TEM IID AtmosphericWiring Diagram KEY Wiring Diagram Millivolt Units With Mechanical ThermostatWiring Diagram IID Units atmospheric Wiring Diagram IID Units Low NOx CONTROLS/ADJUSTMENTS/REPLACEMENTS Knob Stop Shown Above is SPA Temperature RangeGeneral Location of Controls Control Panel RemovalDisplay Faults ElectroniccontrolsDisplay Status RP2100 Remote Control Installation Two-Wire Remote OperationThree Wire TWO Function TWO Wire ONE Function ON/OFF onlyPressure Switch Flame ROLL-OUT Safety SwitchHighlimits Honeywell Pilot Robertshaw Pilot Tube Cleaning Procedure Desooting ProcedureUnitherm Governor U.G. Replacement Combustion Chamber RemovalSTART-UP Procedures S8610B BurneradjustmentFlame ROLL-OUT Safety Switch OperationBurner Drawer Removal GAS Valve RemovalMain Burner and Orifice Removal Pilot RemovalTrouble Shooting Guide MechanicalforqualifiedservicepersonnelonlyElectrical Standing Pilot Millivolt Raypak Pool or SPA Heater Electrical Check with MV GAS ValveTroubleshooting Honeywell S8600 Electrical Electronic Ignition IIDPage Replacement Parts List RAYPAK,INC12-P Fig# Pilot Assemblies Page Page Page Page Limitedwarranty Raypakresidentialswimmingpoolandspaheaters
Related manuals
Manual 52 pages 42.2 Kb

C-R185A, P-R405A, RP2100 specifications

Raypak is a leading manufacturer in the heating and cooling industry, renowned for its innovative products that cater to both residential and commercial sectors. One of its product lines, the RP2100 series, exemplifies cutting-edge technology and features designed to enhance efficiency and performance in pool heating systems.

The RP2100 models, particularly the P-R185B through R-P405B series, incorporate advanced heat exchanger technology, enabling them to offer exceptional heat transfer efficiency. The titanium heat exchangers are designed for durability and resistance against corrosion, particularly in saltwater environments, ensuring the longevity of the system. These units are engineered for both outdoor and indoor applications, with the versatility to adapt to various heating requirements.

In terms of energy efficiency, the RP2100 series boasts a high coefficient of performance (COP), making them cost-effective solutions for pool heating. They are equipped with digital thermostats that provide accurate temperature control, ensuring consistent heating capabilities while minimizing energy consumption. The inclusion of intelligent controls allows for seamless integration with existing systems and provides users with the ability to schedule heating cycles, further enhancing energy savings.

Moving beyond the RP2100 series, the C-R185B to C-R405B models are specifically tailored for commercial applications, combining robust performance with user-friendly features. These commercial heaters are designed to handle larger volumes of water and are built to withstand the rigors of high-traffic environments, such as resorts and sports complexes. Their vertical design optimizes space and promotes better airflow, which is crucial in high-demand scenarios.

The P-R185BL to P-R405BL and C-R185BL to C-R405BL models feature noise-reducing technology, making them suitable for residential settings where peace and quiet are paramount. They utilize advanced acoustic insulation materials that minimize operational noise without sacrificing performance.

In summary, the Raypak RP2100, P-R185B to R-P405B, C-R185B to C-R405B, P-R185BL to P-R405BL, and C-R185BL to C-R405BL series represent the pinnacle of innovation in pool heating solutions. With their durable construction, energy-efficient designs, and advanced technologies, these models are ideal for users seeking reliability, efficiency, and quiet operation in both residential and commercial environments. Investing in Raypak products ensures superior heating performance, longevity, and overall satisfaction.