Subaru Robin Power Products RGX3510 manual Check the Appliance for Trouble, Check the Insulation

Page 72

11-3 AC VOLTAGE IS NORMAL AT NO-LOAD, BUTTHE LOAD CANNOTBE APPLIED.

11-3-1 CHECK THE ENGINESPEED.

If the engine speed is low, adjustit to the rated r.p.m.

*Refer to Step 11-2-1 for engine speed adjustment.

11-3-2 CHECK THE TOTAL WATTAGE OF APPLIANCES CONNECTED TO THE GENERATOR.

Refer to Section 7 “RANGE OF APPLICATIONS” for the wattageof the appliances. If the generator is over-loaded, reduce the loadto the rated output of the generator.

11-3-3 CHECK THE APPLIANCE FOR TROUBLE.

If the appliance is faulty, repair it.

11-3-4 CHECK IF THE ENGINE IS OVERHEATED.

If thecoolingairinletandlorcoolingairoutletis

cloggedwithdirt,grass,chaffor otherdebris, remove it.

 

Fig. 11-8

11-3-5 CHECK THE INSULATION OF THE

I : \-q+=======

GENERATOR.

 

Stop the engine. Measure the insulation resistance

betweentheliveterminal of thereceptacleand the ground terminal.

If the insulation resistance is less than 1MO, dis- assemblethegeneratorandchecktheinsulation resistance of the stator, rotor and the live parts in the control box. (Refer to Section 8-3.)

Any partwheretheinsulationresistanceisless

than 1MQ: the insulation is faulty and may cause electric leakage.

Replace the faulty part.

11 -4 NO DC OUTPUT

11-4-1 CHECK THE AC OUTPUT.

Check the generator by following Step 11-1-1through Step 11-1-3.

- 69 -

Image 72
Contents Generator Contents No DCOutput Idle ControlOption for60 Hz only Specifications TlOlVNtl3llV3NIDN3 3NIEN3 Perfomance Curves RGXl810 Model RGX2410 RGX1810Output M a Model RGX3510 RGX2410RGX3510 3500W OutputMax 4MODELRGX5510 RGX5510RGX5510 5DC Output Option Features General Description 1EXTERNAL View2CONTROLPANEL RGX1810, RGX2410 50Hz, 60H~-llOV,12OVTYPERGX1810, RGX2410 50Hz, 60H~-220V,240V Type RGXl810, RGX2410 50Hz,60Hz-11OV/220V, 120V/240V Type RGXl810,2410 50Hz-220V with SpecialreceptacleRGX1810,2410 AUSTRALIA, 50HZ-240V RGX3510 50Hz, 60Hz-1lOV,120V TypeRGX3510 50Hz, 60Hz-220VY 240VTYPE RGX3510 5OHZ, 60Hz-110V/22OVy120V/240V TypeRGX3510 50Hz-220V Withspecialreceptacle RGX3510 AUSTRALIA, 50HZ-240VRGX5510 50Hz, 60Hz-1lOV, 120V Type RGX5510 60H~-220V/240VTYPERGX5510 ~OHZ, 60H~-lIOV/220V,120V/240V Type RGX5510 50Hz-220V with Special ReceptacleRGX5510 AUSTRALIA, 50Hz-240V Location of Serial Number and Specification Number Constructionandfunction ConstructionFunction StatorCondenser Rotor4DC Fuse Option NO-FUSEBREAKERRGX55 0 r \vJ Receptacle and AC Plug STD.SPECGenerator Operation 1GENERATION Of NO-LOADVOLTAGEVoltage Fluctuations Under Load 3FULL Power Switch Dual voltage type RGX1810,2410,3510Dual voltagetype RGX5510 Page 4ELECTRONICIGNITIONSYSTEM Ignition Timing Plug Flywheel Cooling FANPower supply OIL Sensor 1DESCRIPTIONPrinciple of Sensingoillevel 3HOW Itoperates4BLOCK Diagram of the Circuit Judgement of oil levelDecision of oil shortage Automatic stopof enginePage Safety Precautions Do not place inflammable materialsnear the generatorIncandescent lamp, heater,etc. with a power factor of 1.O Mercury lamps with a smaller power factorAppliances without any indication as to power consumption Fluorescent lamp37/0.26 Measuring Procedures SpecificationsMeasuringinstruments 1 Dr. Robin Generator TesterAmmeters Instruments5oov AC Output Measuring DcoutputmeasuringMeasuring Insulation Resistance StatorControl Panel Checkingfunctionalmembers Voltmeter2AC Receptacles 4STATOR 3NO-FUSE Breaker5ROTOR Assembly Normal Capacityof Condenser 7DIODE RectifierCheckingtablefordigitalcircuittester OIL SensoroptionDisassembly and Assembly Preparation and Precautions10-2DISASSEMBLY Procedures Control box. See FIg Remove IIi Startor Stator Rotor Remo1.e rhe front cover 10-3ASSEMBLYPROCEDURES 10-3-1FRONTCOVER 120- 140 kgocrn 1‘ \ 8.7- 10.1 ft*lb Tighteningtorque11.3-13.2 N m Kg-cm \ Tt 8.7 10.8 ft4bFix Rear CoverH18 flan, nut Tightening torque Control BOXM8 nut 10-3-7FUEL Tank CHECKING, Disassembly and Reassembly of the Control BOX DisassemblyReassembly Checking of Thecontrolbox Troubleshooting 11-1NO AC Output Checking Condenser Normalcapacity of Condenser Checking StatorRemedy Checking RotorAC Voltge is TOO High or TOO LOW Checking Engine Speed Checking Condenser Check condenser referring to -1-111-2-4CHECKING Rotor Check the Appliance for Trouble Check if the Engine is OverheatedCheck the Insulation GeneratorCheck the Wiring Specification ResistanceCheck the DC Fuse 11 -4-4 Check the Diode Rectifier11-5-1ENGINE- Speedis not Increased When a Loadis Applied Idle Control Option for 60Hz onlyControl Unit Board Engine Speed is not Reduced When Load is OFF SolenoidWiring Diagram RGX1810, RGX2410 llOVGeneratorcontrolbox RGX1810, RGX2410 220VRGXl810, RGX2410 11OV/22OV 120V/240V Generator Control BOXRGX3510 1lOV RGX3510 220V RGX3510 11OV/22OV 120V/240VRGX5510 11OV RGX5510 220VRGX5510 11OV/220V 120V/240V Generator ControlboxEngine Wiring Diagram . Recoil Stater Type Page 25 mm2 Symbols Part Name ISSUEEMD-GS1001