Section 2 — Post Installation Start-up and Adjustments

Air-cooled 8.5 kW Generator

2.7.1 ADDITIONAL CORROSION PROTECTION

Do not make any unnecessary adjustments.

!Factory settings are correct for most applica- tions. However, when making adjustments, be careful to avoid overspeeding the engine.

If this procedure or equipment are not available to you, locate the Generac Dealer nearest you and they can perform the adjustments.

NOTE:

A service fee may be charged for this adjustment.

2.7ENGINE GOVERNOR ADJUSTMENT

If both AC frequency and voltage are correspondingly high or low, adjust the engine governor as follows:

1.Loosen governor clamp bolt.

2.Completely remove the idle spring.

3.With governor arm at wide open throttle position, rotate governor shaft fully clockwise. Tighten clamp bolt to 84 inch-pounds.

4.Start unit and apply full load. Use full load speed adjust screw (Figure 2.4) to adjust frequency to 58 Hz.

5.Remove load, stop engine, loosen the idle adjust screw and reconnect the idle spring.

6.Using your hand, push the governor arm to the closed throttle position. Make sure the idle spring does not stretch at all.

7.Restart the unit.

8.Slowly turn the idle adjust screw to adjust the no- load idle frequency to 63-63.5 Hz.

9.The governor is now set.

Figure 2.4 — Full Load Speed Adjust Screw

Full Load Speed Adjust Screw

Periodically spray all engine linkage parts and brack- ets with corrosion inhibiting spray such as WD-40 or a comparable product.

2.8VOLTAGE REGULATOR

ADJUSTMENT

With the frequency between 62-63 Hertz, slowly turn the slotted potentiometer (Figure 2.5) until line volt- age reads 244-252 volts.

NOTE:

You must remove the access panel on top of the control panel to adjust the voltage regulator.

Figure 2.5 – Voltage Adjustment Potentiometer

NOTE:

The voltage regulator is housed above the genera- tor's control panel. The regulator maintains a volt- age in direct proportion to frequency at a 2-to-1 ratio. For example, at 62 Hertz, line-to-neutral voltage will be 124 volts.

12 Generac® Power Systems, Inc.

Image 14
Contents Installation Introduction Authorized Dealer LocationTroubleshooting General Hazards Electrical Hazards Standards IndexProtection Systems System SET LEDUNPACKING/INSPECTION Your Generator 8.5 kW, V-Twin GT-990 EngineSpecifications GeneratorFuel Consumption Reconfiguring Fuel SystemFuel Requirements Recommendations Transfer Switch Battery InstallationBattery LocationElectrical Checks Check Transfer Switch OperationBefore Initial START-UP Generator Tests Under Load Adjusting the Regulator Natural GAS only Checking Automatic OperationEngine Governor Adjustment Voltage Regulator AdjustmentManual Position BREAK-IN ProcedureAutomatic Transfer Operation Auto PositionSequence of Automatic Operation Manual Transfer OperationLOW OIL Pressure Switch Setting the Exercise TimerTransfer Back to Utility Power Source High Temperature SwitchChecking the Engine OIL Level OverspeedChanging the OIL Filter OIL Change ProcedureChanging the Engine OIL Engine OIL RecommendationsBattery Maintenance Spark PlugsAdjusting Valve Clearance Cooling SystemRemoval from Service OUT of Service ProcedureReturn to Service Corrosion ProtectionService Schedule Be performed by your nearest Generac Authorized DealerTroubleshooting Guide Problem Cause CorrectionMounting Dimensions Electrical Data Customer Connection TX TRANSFORMER, 16 Vac 56 VA & 16 Vac 1 VA Dual SEC 1VA Exploded Views and Parts Lists QTY Description Exploded Views and Parts Lists ADAPTOR, Engine Exploded Views and Parts Lists Description QTY 138 122 KNOB, AIR Cleaner 4417 3930 Circuit Breaker 30 X 2 240V SQD Transfer Switch Home Standby Engine only PURCHASER’S/OWNER’S Warranty Responsibilities Your Warranty Rights and ObligationsMANUFACTURER’S Emission Control System Warranty Coverage Emission Control System Warranty Emission Related Parts Include the FollowingWarranty Schedule This Warranty Shall not Apply to the Following