Generac 004692-0 owner manual Adjusting Valve Clearance, Cooling System

Page 21

Section 4 — Maintenance

Air-cooled 8.5 kW Generator

Lead-acid batteries present a risk of fire because they generate hydrogen gas. The following procedures are to be followed:

DO NOT SMOKE when near the battery;

DO NOT cause flame or spark in battery area; and

Discharge static electricity from your body before touching the battery by first touching a grounded metal surface.

Be sure the Auto/Off/Manual switch is set to ! the OFF position before connecting the battery

cables. If the switch is set to AUTO or MANUAL, the generator can crank and start as soon as the battery cables are connected.

Be sure the utility power supply is turned off, or sparking may occur at the battery posts as you attach the cables and cause an explosion.

4.8 ADJUSTING VALVE CLEARANCE

After the first 50 hours of operation, you should adjust the valve clearance in the engine.

Important: If you feel uncomfortable about doing this procedure or you don't have the proper tools, please contact your Generac Authorized Dealer for service assistance. This is a very important step to insure the longest life for your engine.

To adjusting valve clearance:

Make sure the engine is at room temperature.

Make sure that the spark plug wire is removed from the spark plug and out of the way.

Remove the four screws attaching the valve cover with a #2 or #3 phillips screwdriver.

Make sure the piston is at Top Dead Center (TDC) of its compression stroke (both valves closed). To get the piston at TDC, remove the intake screen at the front of the engine to gain access to the flywheel nut. Use a large socket and socket wrench to rotate the nut and hence the engine. While watching the piston through the spark plug hole. The piston should move up and down. The piston is at TDC when it is up as high as it can go.

Loosen the rocker jam nut. Use an 10mm allen wrench to turn the pivot ball stud while checking clearance between the rocker arm and the valve stem with a feeler gauge. Correct clearance is 0.002-0.004 inch (0.05-0.1 mm).

NOTE:

You must hold the rocker arm jam nut in place as you turn the pivot ball stud.

When valve clearance is correct, hold the pivot ball stud in place with the allen wrench and tighten the rocker arm jam nut. Tighten the jam nut to 174 in/lbs. torque. After tightening the jam nut, recheck valve clearance to make sure it did not change.

Figure 4.6 - Valve Clearance Adjustment

Rocker

Pivot BallArm

Stud

Jam Nut

Valve

Stem

Install new valve cover gasket.

Re-attach the valve cover.

NOTE:

Start all four screws before tightening or you will not be able to get all the screws in place. Make sure the valve cover gasket is in place.

Re-attach the spark plug wire to the spark plug.

Repeat the process for the other cylinder.

4.9COOLING SYSTEM

Air inlet and outlet openings in the generator com- partment must be open and unobstructed for contin- ued proper operation. This includes such obstruc- tions as high grass, weeds, brush, leaves and snow.

Without sufficient cooling and ventilating air flow, the engine/generator quickly overheats, which causes it to quickly shut down. (See Figure 4.7 for vent locations.)

Figure 4.7 – Cooling Vent Locations

The exhaust from this product gets extremely hot and remains hot after shutdown. High grass, weeds, brush, leaves, etc. must remain clear of the exhaust. Such materials may ignite and burn from the heat of the exhaust system.

Generac® Power Systems, Inc. 19

Image 21
Contents Installation Authorized Dealer Location IntroductionTroubleshooting General Hazards Standards Index Electrical HazardsSystem SET LED UNPACKING/INSPECTIONProtection Systems 8.5 kW, V-Twin GT-990 Engine Your GeneratorGenerator SpecificationsReconfiguring Fuel System Fuel Requirements RecommendationsFuel Consumption Battery Battery InstallationTransfer Switch LocationCheck Transfer Switch Operation Before Initial START-UPElectrical Checks Generator Tests Under Load Checking Automatic Operation Adjusting the Regulator Natural GAS onlyVoltage Regulator Adjustment Engine Governor AdjustmentAutomatic Transfer Operation BREAK-IN ProcedureManual Position Auto PositionManual Transfer Operation Sequence of Automatic OperationTransfer Back to Utility Power Source Setting the Exercise TimerLOW OIL Pressure Switch High Temperature SwitchOverspeed Checking the Engine OIL LevelChanging the Engine OIL OIL Change ProcedureChanging the OIL Filter Engine OIL RecommendationsSpark Plugs Battery MaintenanceCooling System Adjusting Valve ClearanceReturn to Service OUT of Service ProcedureRemoval from Service Corrosion ProtectionBe performed by your nearest Generac Authorized Dealer Service ScheduleProblem Cause Correction Troubleshooting GuideMounting Dimensions Electrical Data Customer Connection TX TRANSFORMER, 16 Vac 56 VA & 16 Vac 1 VA Dual SEC 1VA Exploded Views and Parts Lists QTY Description Exploded Views and Parts Lists ADAPTOR, Engine Exploded Views and Parts Lists Description QTY 138 122 KNOB, AIR Cleaner 4417 3930 Circuit Breaker 30 X 2 240V SQD Transfer Switch Home Standby Engine only Your Warranty Rights and Obligations MANUFACTURER’S Emission Control System Warranty CoveragePURCHASER’S/OWNER’S Warranty Responsibilities Emission Related Parts Include the Following Emission Control System WarrantyThis Warranty Shall not Apply to the Following Warranty Schedule