Generac 004692-0 owner manual Checking the Engine OIL Level, Overspeed

Page 18

Section 4 — Maintenance

Air-cooled 8.5 kW Generator

￿ 3.7.3 OVERCRANK

Figure 4.1 – Generator Control Panel

This feature prevents the generator from damaging itself when it continually attempts to start and anoth- er problem, such as no fuel supply, prevents it from starting. The unit will crank and rest for a preset time limit. Then, it will stop cranking, and the LED on the generator control panel will light indicating an over- crank failure. The Auto/Off/Manual switch will need to be set to OFF and then back to AUTO to reset the generator control board.

NOTE:

FUSE

 

5A

OFF MAN.

AUTO

FUSE

 

15A

SET

 

EXERCISE

 

TIME

L o c a t e y o u r n e a r e s t d e a le r a t :

POWER SYSTEMS, INC.

SYSTEM SET

LOW OIL

HIGH TEMP.

OVER SPEED

OVER CRANK

F L A S H IN G G R E E N L E D =

N O U T IL IT Y S E N S E 4 F L A S H IN G R E D L E D S =

E X E R C IS E R N O T S E T

If the fault is not repaired, the overcrank feature will continue to activate.

4.2CHECKING THE ENGINE OIL LEVEL

3.7.3.1 Approximate Crank Cycle Times

15 seconds ON

7 seconds OFF

7 seconds ON

7 seconds OFF

Repeat for 45 seconds Approximately 90 seconds total

￿3.7.4 OVERSPEED

This feature protects the generator from damage by shutting it down if it happens to run faster than the preset limit. This protection also prevents the gener- ator from supplying an output that could potentially damage appliances connected to the generator cir- cuit. Contact your nearest Generac Authorized Dealer if this failure occurs.

4.1FUSE

The generator panel’s 15 amp fuse (Figure 4.1) pro- tects the DC control circuit against overload. The fuse is wired in series with the battery output lead to the panel. If the fuse element has melted open, you can- not crank or start the engine. You should replace the fuse using only an identical 15-amp replacement.

The generator panel’s 5 amp fuse protects the battery charge circuit against overload. If the fuse element has melted open, you will not have battery charging capability. You should replace the fuse using only an identical 5 amp replacement. To remove fuse, push cap down and rotate counterclockwise.

For oil capacities, see “Specifications,” Section 1.5 (Page 6). For engine oil recommendations, see Section 4.3.1. To check the engine oil level, proceed as follows (Figure 4.2, on page 17):

1.Start the generator by moving the Auto/ Off/Manual switch to the MANUAL position. Allow it to run for a short while and then shut it down by moving the switch to the OFF position.

2.Remove the dipstick and wipe it dry with a clean cloth.

3.Install the dipstick; then, remove it again. The oil level should be at the dipstick “Full” mark. If nec- essary, add oil to the “Full” mark only. DO NOT FILL ABOVE THE “FULL” MARK.

Never operate the engine with the oil level

!below the “Add” mark on the dipstick. Doing this could damage the engine.

4.Install the dipstick.

5.Reset the Auto/Off/Manual switch to its original position.

Figure 4.2 — Oil Dipstick and Fill, 8.5 kW

Oil Dipstick

Oil Fill

16 Generac® Power Systems, Inc.

Image 18
Contents Installation Introduction Authorized Dealer LocationTroubleshooting General Hazards Electrical Hazards Standards IndexSystem SET LED UNPACKING/INSPECTIONProtection Systems Your Generator 8.5 kW, V-Twin GT-990 EngineSpecifications GeneratorReconfiguring Fuel System Fuel Requirements RecommendationsFuel Consumption Transfer Switch Battery InstallationBattery LocationCheck Transfer Switch Operation Before Initial START-UPElectrical Checks Generator Tests Under Load Adjusting the Regulator Natural GAS only Checking Automatic OperationEngine Governor Adjustment Voltage Regulator AdjustmentManual Position BREAK-IN ProcedureAutomatic Transfer Operation Auto PositionSequence of Automatic Operation Manual Transfer OperationLOW OIL Pressure Switch Setting the Exercise TimerTransfer Back to Utility Power Source High Temperature SwitchChecking the Engine OIL Level OverspeedChanging the OIL Filter OIL Change ProcedureChanging the Engine OIL Engine OIL RecommendationsBattery Maintenance Spark PlugsAdjusting Valve Clearance Cooling SystemRemoval from Service OUT of Service ProcedureReturn to Service Corrosion ProtectionService Schedule Be performed by your nearest Generac Authorized DealerTroubleshooting Guide Problem Cause CorrectionMounting Dimensions Electrical Data Customer Connection TX TRANSFORMER, 16 Vac 56 VA & 16 Vac 1 VA Dual SEC 1VA Exploded Views and Parts Lists QTY Description Exploded Views and Parts Lists ADAPTOR, Engine Exploded Views and Parts Lists Description QTY 138 122 KNOB, AIR Cleaner 4417 3930 Circuit Breaker 30 X 2 240V SQD Transfer Switch Home Standby Engine only Your Warranty Rights and Obligations MANUFACTURER’S Emission Control System Warranty CoveragePURCHASER’S/OWNER’S Warranty Responsibilities Emission Control System Warranty Emission Related Parts Include the FollowingWarranty Schedule This Warranty Shall not Apply to the Following