Generac 004692-0 owner manual Troubleshooting Guide, Problem Cause Correction

Page 24

Section 5 — Troubleshooting

Air-cooled 8.5 kW Generator

5.1TROUBLESHOOTING GUIDE

PROBLEM

CAUSE

CORRECTION

The engine will not crank.

1.

Fuse blown

1.

Replace fuse.

 

2.

Loose, corroded or defective

2.

Tighten, clean or replace

 

 

battery cables

 

as necessary.

 

3.

Defective starter contactor

3.

*

 

4.

Defective starter motor

4.

*

 

5.

Dead Battery

5.

Charge or replace battery.

 

 

 

 

 

The engine cranks but

1.

Out of fuel

1.

Replenish fuel.

will not start.

2.

Defective fuel solenoid (FS)

2.

*

 

3.

Open #14 wire from

3.

*

 

 

engine control board

 

 

 

4.

Defective spark plug(s)

4.

Clean, re-gap or replace plug(s).

 

5.

Valve Lash

5.

Reset Valve Lash.

 

 

 

 

 

The engine starts hard

1.

Air cleaner

1.

Check, replace air cleaner.

and runs rough.

 

plugged or damaged

 

 

 

2.

Defective spark plug(s)

2.

Clean, re-gap or replace plug(s).

 

3.

Fuel regulator not set.

3.

Set fuel regulator.

 

4.

Fuel pressure incorrect.

4.

Confirm fuel pressure to generator

 

 

 

 

is 11-14” WC (0.6 PSI)

 

 

 

 

 

The Auto/Off/Manual switch

1.

Defective switch

1.

*

is set to OFF, but the engine

2.

Auto/Off/Manual switch

2.

*

continues to run.

 

wired incorrectly

 

 

 

3.

Defective control board

3.

*

 

 

 

 

 

There is no AC output from

1.

Main line circuit breaker open

1.

Reset circuit breaker

the generator.

 

 

 

to ON (or closed).

 

2.

Generator internal failure

2.

*

 

 

 

 

 

There is no transfer to

1.

Defective transfer switch coil

1.

*

standby after utility

2.

Defective transfer relay

2.

*

source failure.

3.

Transfer relay circuit open

3.

*

 

4.

Defective control logic board

4.

*

 

 

 

 

 

Unit consumes large

1.

Break-in procedure

1.

*

amounts of oil.

 

not followed (see Section 2.1)

 

 

*Contact your nearest Generac Authorized Dealer for assistance.

22 Generac® Power Systems, Inc.

Image 24
Contents Installation Introduction Authorized Dealer LocationTroubleshooting General Hazards Electrical Hazards Standards IndexSystem SET LED UNPACKING/INSPECTIONProtection Systems Your Generator 8.5 kW, V-Twin GT-990 EngineSpecifications GeneratorReconfiguring Fuel System Fuel Requirements RecommendationsFuel Consumption Battery Installation BatteryTransfer Switch LocationCheck Transfer Switch Operation Before Initial START-UPElectrical Checks Generator Tests Under Load Adjusting the Regulator Natural GAS only Checking Automatic OperationEngine Governor Adjustment Voltage Regulator AdjustmentBREAK-IN Procedure Automatic Transfer OperationManual Position Auto PositionSequence of Automatic Operation Manual Transfer OperationSetting the Exercise Timer Transfer Back to Utility Power SourceLOW OIL Pressure Switch High Temperature SwitchChecking the Engine OIL Level OverspeedOIL Change Procedure Changing the Engine OILChanging the OIL Filter Engine OIL RecommendationsBattery Maintenance Spark PlugsAdjusting Valve Clearance Cooling SystemOUT of Service Procedure Return to ServiceRemoval from Service Corrosion ProtectionService Schedule Be performed by your nearest Generac Authorized DealerTroubleshooting Guide Problem Cause CorrectionMounting Dimensions Electrical Data Customer Connection TX TRANSFORMER, 16 Vac 56 VA & 16 Vac 1 VA Dual SEC 1VA Exploded Views and Parts Lists QTY Description Exploded Views and Parts Lists ADAPTOR, Engine Exploded Views and Parts Lists Description QTY 138 122 KNOB, AIR Cleaner 4417 3930 Circuit Breaker 30 X 2 240V SQD Transfer Switch Home Standby Engine only Your Warranty Rights and Obligations MANUFACTURER’S Emission Control System Warranty CoveragePURCHASER’S/OWNER’S Warranty Responsibilities Emission Control System Warranty Emission Related Parts Include the FollowingWarranty Schedule This Warranty Shall not Apply to the Following