Section 4 — Maintenance

Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators

Figure 4.3 – Engine Air Cleaner

4.6 MISCELLANEOUS MAINTENANCE

Air Cleaner

‹ 4.6.1 CLEANING THE GENERATOR

(Doors Removed for Clarity)

See the “Scheduled Maintenance,” Section 4.7, for air cleaner maintenance.

‹4.5.12 SPARK PLUGS

Reset the spark plug gap or replace the spark plugs as necessary. See Section 4.7.

1.Clean the area around the base of the spark plugs to keep dirt and debris out of the engine. Clean by scraping or washing using a wire brush and com- mercial solvent. Do not blast the spark plugs to clean.

2.Remove the spark plugs and check the condition. Replace the spark plugs if worn or if reuse is questionable. See the “Scheduled Maintenance,” Section 4.7, for recommended inspection.

3.Check the spark plug gap using a wire feeler gauge. Adjust the gap to 0.5-0.6 mm (0.020-0.025 inch) by carefully bending the ground electrode (Figure 4.4).

Figure 4.4 – Setting the Spark Plug Gap

SET PLUG GAP AT 0.5-0.6 mm

(0.020-0.025 inch)

‹4.5.13 COOLANT CHANGE

Every year, have Authorized Service Facility drain, flush and refill the cooling system. See SPECIFICA- TIONS (Section 1.10) for cooling system recommen- dations.

Keep the generator as clean and as dry as possible. Dirt and moisture that accumulates on internal gen- erator windings have an adverse effect on insulation resistance.

Periodically clean generator exterior surfaces. A soft brush may be used to loosen caked on dirt. Use a vacuum system or dry, low pressure air to remove any accumulations of dirt. The generator is housed inside an all-weather enclosure, clean the enclosure with a soft, damp cloth or sponge and water. Apply a coat of automotive type wax once a year to help pre- vent corrosion.

Once each year, have the generator cleaned and inspected by an Authorized Service Dealer. That deal- er will use dry, low pressure air to clean internal windings. Parts inside the control console should be cleaned and inspected at this time as well.

Finally, have the insulation resistance of stator and rotor windings checked. If insulation resistances are excessively low, the generator may require drying.

‹4.6.2 BATTERY

All lead-acid storage batteries discharge when not in use. Refer to specific instructions and warnings that accompany the battery. If such information is not available, observe the following precautions when handling a battery:

DO NOT use jumper cables and a booster battery to crank or start the generator engine.

DO NOT recharge a weak battery while it is installed in the generator. Remove battery from generator and recharge in a well-ventilated area, away from fuel vapors, sparks, heat or flames.

Battery electrolyte fluid is an extremely caustic sulfuric solution that can cause severe burns. DO NOT permit fluid to contact eyes, skin, clothing, painted surfaces, wiring insulation, etc. If any bat- tery fluid is spilled, flush the affected area with clear water immediately.

Always wear safety glasses, rubber apron and gloves when handling a battery.

Batteries give off explosive hydrogen gas while charging. The gas can form an explosive mixture around the battery for several hours after charging. Any spark, heat or flames can ignite the gas and cause an explosion which can shatter the battery, causing blindness or other serious injury.

Generac® Power Systems, Inc. 17

Image 19
Contents Liquid-cooled, Prepackaged Standby Generators Introduction Authorized Service Dealer Location‹ Operation and Maintenance ‹ HOW to Obtain ServiceIntroduction IFC Safety Rules General Hazards Electrical Hazards Generator AC Connection Systems Transfer SwitchGenerator Automatic System OperationEngine Protective Devices ‹ 1.7.1 LOW OIL Pressure Switch‹ 1.7.2 High Coolant Temperature Switch ‹ 1.7.3 LOW Coolant Level SwitchLifting the Generator Unpacking‹ 1.10.2 Engine Specifications SpecificationsReconfiguring the Fuel System ‹ 1.10.1 Generator SpecificationsEngine OIL Recommendations Torque SpecificationsCoolant Recommendations ‹ 2.1.1 Nfpa Standards Generator Mounting SupportBasic Standby Electric System Generator LocationGrounding the Generator Transfer Switch Start Signal ConnectionsEmergency Circuit Isolation Method Total Circuit Isolation Method‹ 2.11.1 Prior to Initial START-UP Battery InstallationPreparation Before START-UP ‹ 2.10.1 Vented BatteriesControl Console Components Using a Standard GTS Transfer SwitchWeekly Exercise Cycle Manual Transfer START-UP Automatic OperationEngine Heater Overload Protection for Engine DC Electrical System Cooling SystemChecking Fluid Levels ‹ 4.5.6 Perform Visual Inspection ‹ 4.5.11 Changing the Engine AIR Cleaner‹ 4.5.4 Inspect Cooling System ‹ 4.5.5 Check Engine Coolant Level‹ 4.5.13 Coolant Change Miscellaneous Maintenance‹ 4.6.4 Battery Replacement ‹ 4.6.3 Battery MaintenanceService Maintenance Interval Information Scheduled MaintenanceLevel Maintenance Level Problem Cause Correction Troubleshooting PointsGuardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators Installation Diagram Section DC-VR Customer Connection 120/240V 1-PHASE Electrical Data ASM Motor Stepper Housing Governor ConnectorConnector Interface Assembly Cover Connector HousingWasher Flat 5/16 Zinc BASE,MOUNTING 1.5L STNRD&ACSTCWasher Shakeproof EXT 5/16 STL Dampener VibrationRoof Cover Cable Weld Stud Under Roof ACSTC&STND Cmprtmnt 1.5L Assembly BASE-DOOR Ground WireGRD Wire Assy 99HSB Assembly Cover AccessWeld Stud Under Roof Panel for Access Cover Cable BRACE, Side 1.5L Mitsu ASSEMBLY,BASE-DOOR Ground WireROOF, ACSTC&STND Cmprtmnt 1.5L SUPPORT, Radiator 1.5L MitsuTo a Silksc Wire AssemblyScrew Hhtt M5-0.8 X 12 BP Washer Flat #10 ZincHardware ENGINE-1.5L Switch OIL PressureARM Adjust Alternator Ground Wire Starter16 7 Guard FAN 1.5L Modine Tank Coolant RecoveryRadiator 1.5L Venturi 1.5L ModineVapor Flange Fuel Inlet Cover AIR CleanerGASKET, AIR Cleaner Adapter Weldment Mounting BaseTo Engine Crankshaft Assy Rotor 20KW Housing BlowerAssy Rotor 10KW Assy Rotor 15KWBattery Post Cover RED+ ASSY,WIRE#16 REDBOOT, Battery Cable BRACKET, Battery Hold DownPIPE,EXHAUST 1.5L STNDRD&ACSTC Manifold Exhaust 1.5LNipple TOE 1.5NPTX5.5 BLK Iron Saddle 2 InchMANUFACTURER’S Emission Control System Warranty Coverage Your Warranty Rights and ObligationsPURCHASER’S/OWNER’S Warranty Responsibilities Emission Related Parts Include the Following Emission Control System WarrantyThis Warranty Shall not Apply to the Following Warranty Schedule

0047210, 0047220, 0047230, 0047240, 0047250, 0047251, 0047252, 0047253, 0047260 specifications

Generac is renowned for its innovation in the power generation industry, and their range of generators—including models 0047210, 0047220, 0047230, 0047240, 0047250, 0047251, 0047252, 0047253, and 0047260—showcase advanced technologies and functionality that meet diverse power needs.

One of the standout features of these models is the use of Generac’s G-Force Engine, specifically designed for reliability and longevity. This engine is notorious for its durability, capable of handling demanding workloads and proving to be more efficient than typical engines found in similar generators. It provides quick start times, lower emissions, and is built to withstand extended operational cycles.

Another notable technology in these models is the Quiet-Test™ mode, which enables the generator to run at a lower RPM while it performs an exercise routine. This feature not only reduces noise during operation but also conserves fuel, making it an eco-friendly option that doesn’t compromise on performance.

The generators are equipped with advanced monitoring and control features, including the Mobile Link™ application compatibility. This allows users to monitor the status of their generator remotely via a smartphone or tablet, offering peace of mind and real-time access to the generator's operational functioning. This connectivity also enables the user to receive alerts and notifications about maintenance needs or when the generator is in need of attention.

In terms of design, these models boast a robust steel enclosure that offers superior protection against the elements, thereby enhancing durability and ensuring efficient operation regardless of weather conditions. The enclosures also come with a weather-resistant finish, making them suitable for outdoor installation.

Moreover, the generators feature a well-thought-out installation process with easily accessible controls and noise-reduction technology, which helps minimize disturbances for residential applications. They also offer multiple power outputs, catering to varied energy needs, from essential home appliances to larger devices.

Safety is a core consideration with Generac models, and features such as the automatic shutdown mechanism prevent overheating, ensuring operational safety during use. Coupled with an efficient fuel consumption rate, these generators stand out as impeccable solutions for power backup in homes and businesses alike.

The series exemplifies Generac’s commitment to excellence in power solutions, integrating user-friendly technology, efficient performance, and top-tier safety into compact, durable designs. Users can rely on models 0047210 to 0047260 for dependable power generation tailored to their specific needs.