Briggs & Stratton 01917-0, 01918-0 System Operation, Testing the Automatic Transfer Switch

Page 9

Briggs & Stratton Power Products Automatic Transfer Switch

Installation and Owner’s Manual

SYSTEM OPERATION

To select automatic transfer operation, do the following:

1.Set circuit breaker that sends utility power to transfer switch to “On” position.

2.Set generator’s main circuit breaker to its “On” position.

3.Install 15 Amp fuse in control panel on generator.

4.Set AUTO/OFF/MANUAL switch on generator to “AUTO” position.

The system will now be in automatic operation mode.

TESTING THE AUTOMATIC TRANSFER SWITCH

Turn the circuit breaker feeding the transfer switch, to the “Off” position.The automatic sequence will follow.To go back to utility power, turn the circuit breaker to the “On” position.

Automatic Sequence

Utility Fail

Utility voltage sensor senses when utility voltage is below 70 percent of nominal. Engine start sequence is initiated after 6 second time delay.

Engine Warm-Up

Time delay to allow for engine warm-up before transfer fixed at 20 seconds or 50 seconds with optional cold weather package.

Transfer

Transfers from utility to standby supply occurs after standby voltage is above set levels. Minimum engine run time is 4 minutes after transfer.

Utility Pickup

Voltage pickup level is 80 percent of nominal voltage.

Retransfer

Retransfer from standby to utility supply 10 seconds after utility voltage supply is above pickup level.

Engine Cool Down

Engine will run for 60 seconds after retransfer.

Specifications

UL® 1008 Listed Transfer Switch

Model 01917

Enclosure . . . . . . . . . . . . . . . . . . . NEMA 1

Maximum Load/Circuit:

from Load Center . . . . . . . . . . 50 Amps Rated AC Voltage. . . . . . . . . . . . . 250 Volts Poles . . . . . . . . . . . . . . . . . . . . . . 2 Frequency . . . . . . . . . . . . . . . . . . 50/60 Hz

Fault Current Rating . . . . . . . . . . 5,000 RMS Symmetrical Amperes

Weight . . . . . . . . . . . . . . . . . . . . . 27 lbs.

Model 01918

Enclosure . . . . . . . . . . . . . . . . . . . NEMA 3R

Maximum Load/Circuit:

from Load Center . . . . . . . . . . 50 Amps Rated AC Voltage. . . . . . . . . . . . . 250 Volts Poles . . . . . . . . . . . . . . . . . . . . . . 2 Frequency . . . . . . . . . . . . . . . . . . 50/60 Hz

Fault Current Rating . . . . . . . . . . 5,000 RMS Symmetrical Amperes

Weight . . . . . . . . . . . . . . . . . . . . . 34 lbs.

When Calling the Factory

Before contacting Briggs and Stratton Power Products regarding service or repair of this transfer switch, obtain the Model Number and Serial Number from the unit data decal located on or inside the case.

To contact Briggs and Stratton Power Products call 1-800-743-4115, between 8:00 AM and 5:00 PM CT.

9

Image 9
Contents Installation Table of Contents Only qualified electricians should attempt installation Safety RulesFor the Home Owner IntroductionInstallation Shipment ContentsDelivery Inspection Isolation Essential CircuitMounting Guidelines Distribution Neutral System Operation Testing the Automatic Transfer SwitchBriggs & Stratton Power Products Automatic Transfer Switch Problem Cause Correction TroubleshootingTransfer Switch Schematic Transfer Switch Wiring Diagram Transfer Switch Exploded View & Parts List NemaDescription Nema 3R Briggs & Stratton Power Products Automatic Transfer Switch Limited Warranty Table DES Matières Guide dinstallation et dutilisationAvertissement Introduction Au Détaillant ou à lEntrepreneur Procédant à lInstallationAu Propriétaire Résidentiel Conseils au PropriétaireResponsabilités de lInstallateur InstallationDescription de lÉquipement DéballageSchéma dun Système Typique avec les Circuits Essentiels Isolation DES Circuits EssentielsInterconnexions du Câblage dAlimentation Instructions dinstallationSerre Mise À Lessai DU Commutateur DE Transfert Automatique FonctionnementSéquence Automatique CaractéristiquesManual de Instalación y del Propietario RemarquesDépannage Guide dinstallation et dutilisation Garantie Limitée Prueba DEL Conectador Automático Tabla DE ContenidoPrecaución AdvertenciaIntroducción Orientación para el PropietarioPara el Propietario Doméstico Responsabilidades del Instalador InstalaciónDescripción del Equipo DesempaqueAislamiento DE LOS Circuitos Fundamentales Instrucciones de Montaje Interconexiones de Cableado de EnergíaConexión al Generador Prueba DEL Conectador Automático FuncionamientoEspecificaciones Secuencia AutomáticaNotas Reparacion DE Averias Problemo Causa AccionGarantía Limitada