OPERATION
Stopping the Engine
1.Turn OFF and unplug all electrical loads from generator panel receptacles. NEVER start or stop engine with electrical devices plugged in and turned ON.
2.Let engine run at
3.Turn engine off according to instructions given in the engine operator’s manual.
4.Move fuel valve to “Off” position.
RECEPTACLES
CAUTION
Receptacles may be marked with rating value greater than generator output capacity.
•NEVER attempt to power a device requiring more amperage than generator or receptacle can supply.
•DO NOT overload the generator. See “Don’t Overload Generator”.
120 Volt AC, 30 Amp Locking Receptacle
Use a NEMA
Figure 5 — 120 Volt AC, 30 Amp, Locking Receptacle
NEMA L5-30
Neutral 120V Hot
Ground (Green)
Use this receptacle to operate 120 Volt AC, 60 Hz, single phase loads requiring up to 3,250 watts (3.25 kW) of power at 27.1 Amps. The outlet is protected by a
120 Volt AC, 20 Amp, Duplex Receptacles
Each duplex receptacle (Figure 6) is protected against overload by a
Figure 6 — 120 Volt, 20 Amp Duplex Receptacle
Use each receptacle to operate 120 Volt AC,
COLD WEATHER
OPERATION
Under certain weather conditions (temperatures below 40°F [4°C] combined with high humidity), your generator may experience icing of the carburetor and/or the crankcase breather system. To reduce this problem, you need to perform the following:
1.Make sure generator has clean, fresh fuel.
2.Open fuel valve (turn valve to open position).
3.Use SAE
4.Check oil level daily or after every eight (8) hours of operation.
5.Maintain generator following “Maintenance Schedule” in engine operator’s manual.
6.Shelter unit from elements.
10